| 2022-07-07 11:17:45 | PLAN REVIEW BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | BU1635 BN4338 |
| | ASFPM CFM US-21-11935 |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. VALUE |
| | PROVIDE AN ESTIMATED SQUARE FOOTAGE OF STUCCO. |
| | |
| | CITY OF WPB CHPT.1 VALUE |
| | 109.3 BUILDING PERMIT VALUATIONS. |
| | |
| | 1A. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE |
| | OF WORK. |
| | 1B. THE PERMIT VALUATION AND PERMIT FEE MUST BE |
| | COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED |
| | CONTRACTOR WOULD PROVIDE. THIS INCLUDES ALL LABOR, |
| | MATERIALS AND RENTALS OF EQUIPMENT TO PERFORM THE SCOPE |
| | OF WORK. |
| | 1C. YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY |
| | THE OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT |
| | RENTAL TO VERIFY VALUE. |
| | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 2.PROVIDE A DETAIL OF THE PROPOSED STUCCO SYSTEM TO BE |
| | APPLIED. IDENTIFY WALL TYPE (WOOD/CMU). |
| | EACH STUCCO SYSTEM SHALL INCLUDE THE FOLLOWING: |
| | |
| | R703.2WATER-RESISTIVE BARRIER. (HOUSE WRAP) |
| | ONE LAYER OF NO. 15 ASPHALT FELT, FREE FROM HOLES AND |
| | BREAKS, COMPLYING WITH ASTM D226 FOR TYPE 1 FELT OR |
| | OTHER APPROVED WATER-RESISTIVE BARRIER SHALL BE APPLIED |
| | OVER STUDS OR SHEATHING OF ALL EXTERIOR WALLS. NO. 15 |
| | ASPHALT FELT SHALL BE APPLIED HORIZONTALLY, WITH THE |
| | UPPER LAYER LAPPED OVER THE LOWER LAYER NOT LESS THAN 2 |
| | INCHES (51 MM). WHERE JOINTS OCCUR, FELT SHALL BE |
| | LAPPED NOT LESS THAN 6 INCHES (152 MM). OTHER APPROVED |
| | MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| | WATER-RESISTIVE BARRIER MANUFACTURER?S INSTALLATION |
| | INSTRUCTIONS. THE NO. 15 ASPHALT FELT OR OTHER APPROVED |
| | WATER-RESISTIVE BARRIER MATERIAL SHALL BE CONTINUOUS TO |
| | THE TOP OF WALLS AND TERMINATED AT PENETRATIONS AND |
| | BUILDING APPENDAGES IN A MANNER TO MEET THE |
| | REQUIREMENTS OF THE EXTERIOR WALL ENVELOPE AS DESCRIBED |
| | IN SECTION R703.1. THE WATER RESISTIVE BARRIER IS NOT |
| | REQUIRED FOR DETACHED ACCESSORY BUILDINGS. |
| | |
| | R703.7.1LATH. (PAPER BACKED) |
| | LATH AND LATH ATTACHMENTS SHALL BE OF |
| | CORROSION-RESISTANT MATERIALS. EXPANDED METAL OR WOVEN |
| | WIRE LATH SHALL BE ATTACHED WITH 11/2-INCH-LONG (38 |
| | MM), 11 GAGE NAILS HAVING A 7/16-INCH (11.1 MM) HEAD, |
| | OR 11/2-INCH-LONG (22.2 MM), 16 GAGE STAPLES, SPACED IN |
| | ACCORDANCE WITH ASTM C1063 OR C1787, OR AS OTHERWISE |
| | APPROVED. |
| | |
| | R703.7.2PLASTER. |
| | PLASTERING WITH CEMENT PLASTER SHALL BE NOT LESS THAN |
| | THREE COATS WHERE APPLIED OVER ANY TYPE OF |
| | CODE-APPROVED LATH AND SHALL BE NOT LESS THAN TWO COATS |
| | WHERE DIRECTLY APPLIED OVER MASONRY, CONCRETE, CLAY |
| | BRICK, STONE OR TILE. IF THE PLASTER SURFACE IS |
| | COMPLETELY COVERED BY VENEER OR OTHER FACING MATERIAL |
| | OR IS COMPLETELY CONCEALED, PLASTER APPLICATION NEED BE |
| | ONLY TWO COATS, PROVIDED THE TOTAL THICKNESS IS AS SET |
| | FORTH IN TABLE R702.1(1). |
| | ON WOOD-FRAME CONSTRUCTION WITH AN ON-GRADE FLOOR SLAB |
| | SYSTEM, EXTERIOR PLASTER SHALL BE APPLIED TO COVER, BUT |
| | NOT EXTEND BELOW, LATH, PAPER AND SCREED. CEMENT |
| | PLASTER SHALL BE IN ACCORDANCE WITH ASTM C926. |
| | |
| | R703.7EXTERIOR PLASTER. |
| | INSTALLATION OF THESE MATERIALS SHALL BE IN COMPLIANCE |
| | WITH ASTM C926, ASTM C1063 OR ASTM C1787 AND THE |
| | PROVISIONS OF THIS CODE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |
| | |