| 2022-07-11 08:31:49 | NEW GARAGE AND GUEST HOUSE |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVAL FOR THE OVERHEAD GARAGE DOOR - ALL |
| | PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| | APPROVED BY THE BUILDING DESIGNER OF RECORD OR THE |
| | PRODUCT APPROVAL NUMBER NEEDS TO BE SHOWN ON THE |
| | DRAWINGS. |
| | |
| | 2) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVAL FOR THE ROOF TILE ADHESIVE. |
| | |
| | 3) PLEASE SHOW THE REQUIRED EMERGENCY EGRESS FROM THE |
| | BED ROOMS - WINDOW "C" HAS RAILING BLOCKING THE EGRESS |
| | - WINDOW "A" DOES NOT MEET THE EMERGENCY EGRESS SIZE |
| | FBC R310.1 |
| | |
| | 4) THE DRAWINGS SHOW 1/2 INCH DRYWALL ON THE GARAGE |
| | CEILING - WITH DWELING SPACE ABOVE SHOULD BE 5/8 INCH |
| | PER FBC TABLE R302.6 |
| | |
| | 5) R30 BATT INSULATION MAY NOT HAVE THE 1 INCH |
| | VENTILATION SPACE PER FBC R806.3 VENT AND INSULATION |
| | CLEARANCE. |
| | WHERE EAVE OR CORNICE VENTS ARE INSTALLED, BLOCKING, |
| | BRIDGING AND INSULATION SHALL NOT BLOCK THE FREE FLOW |
| | OF AIR. NOT LESS THAN A 1-INCH (25 MM) SPACE SHALL BE |
| | PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING |
| | AND AT THE LOCATION OF THE VENT. |
| | |
| | 6) ROOF VENTILATION IS REQUIRED PER FBC R806.1 |
| | VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN OR SNOW. |
| | |
| | |