Plan Review Notes
Plan Review Notes For Permit 22050195
Permit Number 22050195
Review Stop B
Sequence Number 1
Notes
Date Text
2022-07-11 08:31:49NEW GARAGE AND GUEST HOUSE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE OVERHEAD GARAGE DOOR - ALL
 PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD OR THE
 PRODUCT APPROVAL NUMBER NEEDS TO BE SHOWN ON THE
 DRAWINGS.
  
 2) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE ROOF TILE ADHESIVE.
  
 3) PLEASE SHOW THE REQUIRED EMERGENCY EGRESS FROM THE
 BED ROOMS - WINDOW "C" HAS RAILING BLOCKING THE EGRESS
 - WINDOW "A" DOES NOT MEET THE EMERGENCY EGRESS SIZE
 FBC R310.1
  
 4) THE DRAWINGS SHOW 1/2 INCH DRYWALL ON THE GARAGE
 CEILING - WITH DWELING SPACE ABOVE SHOULD BE 5/8 INCH
 PER FBC TABLE R302.6
  
 5) R30 BATT INSULATION MAY NOT HAVE THE 1 INCH
 VENTILATION SPACE PER FBC R806.3 VENT AND INSULATION
 CLEARANCE.
 WHERE EAVE OR CORNICE VENTS ARE INSTALLED, BLOCKING,
 BRIDGING AND INSULATION SHALL NOT BLOCK THE FREE FLOW
 OF AIR. NOT LESS THAN A 1-INCH (25 MM) SPACE SHALL BE
 PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING
 AND AT THE LOCATION OF THE VENT.
  
 6) ROOF VENTILATION IS REQUIRED PER FBC R806.1
 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW.
  
  