| 2022-10-05 11:41:38 | 1ST PLUMBING REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FRC P3101 - YOUR WASTE AND VENT SYSTEM IS NOT |
| | TYPICAL. SEVERAL ITEMS DO NOT MEET CODE. THE SHOWER IN |
| | THE MASTER BATH AND THE KING SWEET BATH SHOWER ARE NOT |
| | VENTED (P3101.2.1), THE WATER CLOSET IN THE MASTER BATH |
| | SHOWS THE TRAP (AND A WATER CLOSET TYPICALLY DOES NOT |
| | SHOW THE TRAP ON THE ISO) WITH THE VENT ON THE HIGH |
| | SIDE OF THE TRAP, THE HALL BATH WATER CLOSET AND THE |
| | HALL BATH SHOWER SHOWS AN ILLEGAL DRY VENT (THE VENT |
| | CANNOT BE HORIZONTAL UNTIL IT IS 6" ABOVE THE FLOOD RIM |
| | OF THE FIXTURE SERVED - P3104.4). PLEASE RECONFIGURE |
| | THE DRAIN AND VENT SYSTEM TO SHOW A COMPLIANT SYSTEM. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |