| Plan Review Notes For Permit 22050161 |
| Permit Number |
22050161 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-10-05 10:24:25 | THE MECHANICAL EQUIPMENT SIZE HAS BEEN CORRECTED. I DO | | | NOT SEE THE LOCATION OF THE AHU OR THE DUCT SIZES WITH | | | THE CFM'S REQUIRED AT EACH GRILLE. | | | PLEASE ADDRESS COMMENT 2 OF PREVIOUS REVIEW COMMENTS. | | | | | | 2) REVISE THE MECHANICAL DRAWING TO IDENTIFY THE AHU | | | LOCATION, PROVIDE DUCT SIZES ON ALL DUCTWORK, PROVIDE | | | CFM?S AND GRILLE SIZES FOR ALL GRILLES. FBC 107.2.1 | | | THE MECHANICAL DRAWING DOES NOT HAVE JOSEPH SIMMONS | | | DIGITAL SIGNATURE. PROVIDE THE ORIGIMAL DIGITAL | | | SIGNATURE FROM THE DESIGNER. 471/481 |
|