Plan Review Notes
Plan Review Notes For Permit 22050161
Permit Number 22050161
Review Stop M
Sequence Number 2
Notes
Date Text
2022-10-05 10:24:25THE MECHANICAL EQUIPMENT SIZE HAS BEEN CORRECTED. I DO
 NOT SEE THE LOCATION OF THE AHU OR THE DUCT SIZES WITH
 THE CFM'S REQUIRED AT EACH GRILLE.
 PLEASE ADDRESS COMMENT 2 OF PREVIOUS REVIEW COMMENTS.
  
 2) REVISE THE MECHANICAL DRAWING TO IDENTIFY THE AHU
 LOCATION, PROVIDE DUCT SIZES ON ALL DUCTWORK, PROVIDE
 CFM?S AND GRILLE SIZES FOR ALL GRILLES. FBC 107.2.1
 THE MECHANICAL DRAWING DOES NOT HAVE JOSEPH SIMMONS
 DIGITAL SIGNATURE. PROVIDE THE ORIGIMAL DIGITAL
 SIGNATURE FROM THE DESIGNER. 471/481