| Plan Review Notes For Permit 22050161 |
| Permit Number |
22050161 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-11-02 10:27:33 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 2.) FBC B 107.2.1, PLAN SHEET A-4 (PORTICO DETAIL) IS | | | NOT CLEAR FOR THE FOOTINGS AS THE FOOTING WIDTH APPEARS | | | TO SHOW TWO DIFFERENT WIDTH MEASUREMENTS OF 18" TYPICAL | | | NOTE AND 22" MEASUREMENT INDICATED. PLEASE CORRECT ON | | | PLAN. | | | 3.) FBC B 107.2.1, PLAN SHEET A-4 (PORTICO COLUMNS | | | DETAIL) IS NOT CLEAR AS THESE COLUMNS ARE LOAD BEARING, | | | PLEASE PROVIDE STRUCTURAL DETAIL. | | | 7.) FBC B 107.2.1/FBC B 107.3.4.1/FBC R TABLE | | | 301.2.1.3, PLAN SHEET A-1 (PRODUCT APPROVALS), PLEASE | | | ADD TO TITLE OF PRODUCT APPROVAL SECTION A NOTE | | | INDICATING THAT THESE ARE TO BE DEFERRED SUBMITTALS AND | | | CORRECT THE WINDLOAD SPEEDS FROM 150 VULT & 116 VASD TO | | | 170 VULT & 132 VASD. |
|