| Plan Review Notes For Permit 22050161 |
| Permit Number |
22050161 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-11 10:44:00 | 1ST REVIEW FMC | | | PERMIT: 22050161 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS CALL | | | FOR A 3.5 TON SYSTEM BUT THE MECHANICAL DRAWING | | | SPECIFIES A 5 TON SYSTEM. THE 2 NEED TO BE CONSISTENT. | | | | | | R403.7.1.2.1 HEAT PUMPS. HEAT PUMP SIZING SHALL BE | | | BASED ON THE COOLING REQUIREMENTS AS CALCULATED | | | ACCORDING TO SECTION R403.7.1.1, AND THE HEAT PUMP | | | TOTAL COOLING CAPACITY SHALL NOT BE MORE THAN 1.15 | | | TIMES GREATER THAN THE DESIGN COOLING LOAD EVEN IF THE | | | DESIGN HEATING LOAD IS 1.15 TIMES GREATER THAN THE | | | DESIGN COOLING LOAD. | | | | | | 2) REVISE THE MECHANICAL DRAWING TO IDENTIFY THE AHU | | | LOCATION, PROVIDE DUCT SIZES ON ALL DUCTWORK, PROVIDE | | | CFM?S AND GRILLE SIZES FOR ALL GRILLES. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|