Text |
| 2022-06-22 15:29:14 | ELECTRIC REVIEW FAILED | | | 1) ELECTRIC PANEL IS DETAILED INSIDE A BATHROOM NOT IN | | | COMPLIANCE WITH NEC 240.24 (E). PLEASE RELOCATE IN A | | | NEC COMPLIANT LOCATION. | | | 2) NO OUTDOOR RECEPTACLES ARE DETAILED AT FRONT AND | | | REAR PATIOS AS REQUIRED PER NEC 210.52 (E) (1) AND (3) | | | 3) NO SMOKE ALARM IS DETAILED OUTSIDE MASTER BEDROOM AS | | | REQUIRED PER FBC R314.3 | | | $) RECEPTACLE IS DETAILED IN MASTER BATHROOM SHOWER NOT | | | IN COMPLIANCE WITH NEC 406.9(C) PLEASE REMOVE AS | | | APPLICABLE | | | 6) NO RECEPTACLE IS DETAILED AT POWDER ROOM SINK BASIN | | | AS REQUIRED PER NEC 210.52 (D) PLEASE CORRECT AS | | | APPLICABLE | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|