Plan Review Notes
Plan Review Notes For Permit 22050161
Permit Number 22050161
Review Stop E
Sequence Number 1
Notes
Date Text
2022-06-22 15:29:14ELECTRIC REVIEW FAILED
 1) ELECTRIC PANEL IS DETAILED INSIDE A BATHROOM NOT IN
 COMPLIANCE WITH NEC 240.24 (E). PLEASE RELOCATE IN A
 NEC COMPLIANT LOCATION.
 2) NO OUTDOOR RECEPTACLES ARE DETAILED AT FRONT AND
 REAR PATIOS AS REQUIRED PER NEC 210.52 (E) (1) AND (3)
 3) NO SMOKE ALARM IS DETAILED OUTSIDE MASTER BEDROOM AS
 REQUIRED PER FBC R314.3
 $) RECEPTACLE IS DETAILED IN MASTER BATHROOM SHOWER NOT
 IN COMPLIANCE WITH NEC 406.9(C) PLEASE REMOVE AS
 APPLICABLE
 6) NO RECEPTACLE IS DETAILED AT POWDER ROOM SINK BASIN
 AS REQUIRED PER NEC 210.52 (D) PLEASE CORRECT AS
 APPLICABLE
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  