| Plan Review Notes For Permit 22050110 |
| Permit Number |
22050110 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-17 17:04:57 | 1ST REVIEW FMC | | | PERMIT: 22050110 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET 1 OF 1 INDICATES 308 SQ FT OF REAR PORCH | | | ENCLOSURE A/C. PROVIDE ENERGY CALCULATIONS, MECHANICAL | | | EQUIPMENT SIZING CALCULATIONS, A MECHANICAL DRAWING | | | SHOWING THE MECHANICAL SYSTEM INCLUDING THE CONDENSING | | | UNIT LOCATION AND TIE DOWN METHOD. REVISED THE PLAN TO | | | SHOW THE INSULATION IN THE ROOF OF THIS NEWLY | | | CONDITIONED SPACE. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|