| 2022-05-13 07:24:15 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22050098 |
| | 5/13/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A-118: SHOW THE CLEAR FLOOR SPACE DIAGRAMS |
| | WITH DIMENSIONS FOR THE COFFEE SINK, DISHWASHER, AND |
| | REFRIGERATOR- SECS. 606.2, 804.6.1, 804.6.3, & 804.6.6 |
| | FBC ACC. |
| | |
| | 2) P-201, P-301, P-401: A MEANS OF LIMITING THE HOT |
| | WATER DELIVERY TEMPERATURE AT FIXTURES IS REQUIRED AND |
| | IT CANNOT BE A THERMOSTAT ON A WATER HEATER. A MASTER |
| | THERMOSTATIC OR POINT OF USE MIXING VALVE SHALL BE |
| | INSTALLED- SEC. 607.1.1 FBC P. PLEASE DO NOT CONFUSE |
| | THE CODE REQUIREMENT WITH THE TEMPERED WATER DELIVERY |
| | REQUIRED FOR PUBLIC LAVATORIES. HOT WATER AT A MINIMUM |
| | OF 110 DEGREES F IS REQUIRED AT THE SINK AND |
| | DISHWASHER- SEC. 607.1. |
| | |
| | 3) P-201, P-301: PROVIDE BACKFLOW PREVENTERS AT THE |
| | INDIVIDUAL WATER SUPPLY LINES TO THE DISHWASHER AND |
| | REFRIGERATOR ICE MAKER- SEC. 608.3 FBC P. |
| | |
| | 4) P-401: THE WATER HEATER DRAIN PAN PIPE SHALL |
| | TERMINATE OVER A SUITABLY LOCATED INDIRECT WASTE |
| | RECEPTOR OR FLOOR DRAIN, OR EXTEND TO THE EXTERIOR OF |
| | THE BUILDING AND TERMINATE ABOVE THE ADJACENT GROUND |
| | SURFACE- SEC. 504.7.2 FBC P. |
| | |
| | 5) P-401: PROVIDE UL TESTED AND APPROVED FIRESTOPPING |
| | ASSEMBLIES FOR PIPES PENETRATING THROUGH THE FLOOR |
| | SLAB- SECS. 315.1 FBC P AND 714.4.1.2 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |