| 2022-05-12 16:06:59 | OFFICE RENOVATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE A NOTE ON THE DRAWINGS REFERRING TO | | | THE FIRE CLASSIFICATION FOR THE FLOOR, WALL AND CEILING | | | FINISHES - FBC CHAPTER 8 | | | | | | 2) DRAWING G-002 SHOWS CORRIDOR WALLS ARE 0 FIRE RATED | | | - PLEASE PROVIDE A NOTE AS TO HOW THE ELEVATOR | | | HOISTWAYS ARE PROTECTED - FBC 3006.3 | | | |
|