2022-07-11 11:18:19PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SH WINDOW PRODUCT APPROVAL FL15329-R5 IS FOR
 NON-IMPACT RATED WINDOWS. OPENING PROTECTION IS
 REQUIRED.
 1609.1.2 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, GLAZED OPENINGS IN
 BUILDINGS SHALL BE IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT-RESISTANT COVERING MEETING THE REQUIREMENTS
 OF ANSI/DASMA 115 (FOR GARAGE DOORS AND ROLLING DOORS)
 OR TAS 201, 202 AND 203, AAMA 506, ASTM E1996 AND ASTM
 E1886 REFERENCED HEREIN, OR AN APPROVED
 IMPACT-RESISTANT STANDARD AS FOLLOWS:
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9144 MM) OF
 GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE
 TEST OF ASTM E1996.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  