2022-07-08 08:40:44NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND
 ROOFING SYSTEMS.
  
 2) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB
 107.3.4
  
 3) DRAWING A-3.1 SHOWS DRAFT STOP PLACEMENT IN THE ROOF
 FRAMING - PLEASE SHOW THE LOCATION OF THE DRAFT STOP IN
 THE FLOOR TRUSS FRAMING FBC R302.12 DRAFTSTOPPING.
 IN COMBUSTIBLE CONSTRUCTION WHERE THERE IS USABLE SPACE
 BOTH ABOVE AND BELOW THE CONCEALED SPACE OF A
 FLOOR-CEILING ASSEMBLY, DRAFTSTOPS SHALL BE INSTALLED
 SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED
 1,000 SQUARE FEET (92.9 M2). DRAFTSTOPPING SHALL DIVIDE
 THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS.
  
 4) PLEASE SHOW GENERATOR EXHAUST TO BE 10 FOOT FROM ANY
 BUILDING OPENING - FBC R303.5.1
  
 5) PLEASE SHOW WIND PRESSURES FOR ALL ROOF WIND ZONES
 (1,2E,2R,3) PER FBC R FIGURE R301.2(7)
  
 6) SEPARATE PERMITS ARE REQUIRED FOR - EXISTING
 BUILDING DEMO, SITE WALLS, FENCING, DETACHED ACCESSORY
 STRUCTURE (FITNESS STUDIO BUILDING).