| Plan Review Notes For Permit 22050045 |
| Permit Number |
22050045 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-08 08:40:44 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND | | | ROOFING SYSTEMS. | | | | | | 2) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | | APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB | | | 107.3.4 | | | | | | 3) DRAWING A-3.1 SHOWS DRAFT STOP PLACEMENT IN THE ROOF | | | FRAMING - PLEASE SHOW THE LOCATION OF THE DRAFT STOP IN | | | THE FLOOR TRUSS FRAMING FBC R302.12 DRAFTSTOPPING. | | | IN COMBUSTIBLE CONSTRUCTION WHERE THERE IS USABLE SPACE | | | BOTH ABOVE AND BELOW THE CONCEALED SPACE OF A | | | FLOOR-CEILING ASSEMBLY, DRAFTSTOPS SHALL BE INSTALLED | | | SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED | | | 1,000 SQUARE FEET (92.9 M2). DRAFTSTOPPING SHALL DIVIDE | | | THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS. | | | | | | 4) PLEASE SHOW GENERATOR EXHAUST TO BE 10 FOOT FROM ANY | | | BUILDING OPENING - FBC R303.5.1 | | | | | | 5) PLEASE SHOW WIND PRESSURES FOR ALL ROOF WIND ZONES | | | (1,2E,2R,3) PER FBC R FIGURE R301.2(7) | | | | | | 6) SEPARATE PERMITS ARE REQUIRED FOR - EXISTING | | | BUILDING DEMO, SITE WALLS, FENCING, DETACHED ACCESSORY | | | STRUCTURE (FITNESS STUDIO BUILDING). |
|