Plan Review Notes
Plan Review Notes For Permit 22050042
Permit Number 22050042
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-05-11 12:51:15FIRE PROVISO:
  
 THERE ARE INDICATIONS OF FF PHONE JACKS.
  
 PER NFPA 101, CH 11
  
 11.8 HIGH-RISE BUILDINGS
  
 11.8.4.2 TWO-WAY TELEPHONE SERVICE SHALL BE IN
 ACCORDANCE WITH
 11.8.4.2.1 AND 11.8.4.2.2.
 11.8.4.2.1 TWO-WAY TELEPHONE COMMUNICATION SERVICE
 SHALL BE PROVIDED
 FOR FIRE DEPARTMENT USE. THIS SYSTEM SHALL BE IN
 ACCORDANCE WITH
 NFPA 72. THE COMMUNICATIONS SYSTEM SHALL OPERATE
 BETWEEN THE EMER GENCY COMMAND CENTER AND EVERY
 ELEVATOR CAR, EVERY ELEVATOR LOBBY, AND
 EACH FLOOR LEVEL OF EXIT STAIRS.
 11.8.4.2.2 THE REQUIREMENT OF 11.8.4.2.1 SHALL NOT
 APPLY WHERE THE FIRE
 DEPARTMENT RADIO SYSTEM IS APPROVED AS AN EQUIVALENT
 SYSTEM
  
 FF PHONE JACKS ARE NOT REQUIRED WITH APPROVAL OF
 TWO-WAY RADIO COMMUNICATIONS PER THE AHJ.
  
 PLEASE SCHEDULE A FF PORTABLE RADIO TEST THROUGH THE
 OFFICE OF THE FIRE MARSHAL TO REVIEW RADIO
 COMMUNICATIONS PRIOR TO INSTALLING FF PHONE JACKS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  