Review Stop B
Sequence Number 1
Notes
Date Text
2022-06-24 11:10:40GATES SHALL COMPLY WITH FBC-R4501.17.1.8. ACCESS GATES,
 WHEN PROVIDED, SHALL BE SELF-CLOSING AND SHALL COMPLY
 WITH THE REQUIREMENTS OF SECTIONS R4501.17.1.1 THROUGH
 R4501.17.1.7 AND SHALL BE EQUIPPED WITH A SELF-LATCHING
 LOCKING DEVICE LOCATED ON THE POOL SIDE OF THE GATE.
 WHERE THE DEVICE RELEASE IS LOCATED NO LESS THAN 54
 INCHES (1372 MM) FROM THE BOTTOM OF THE GATE, THE
 DEVICE RELEASE MECHANISM MAY BE LOCATED ON EITHER SIDE
 OF THE GATE AND SO PLACED THAT IT CANNOT BE REACHED BY
 A YOUNG CHILD OVER THE TOP OR THROUGH ANY OPENING OR
 GAP FROM THE OUTSIDE. GATES THAT PROVIDE ACCESS TO THE
 SWIMMING POOL MUST OPEN OUTWARD AWAY FROM THE POOL. THE
 GATES AND BARRIER SHALL HAVE NO OPENING GREATER THAN
 1/2 INCH (12.7 MM) WITHIN 18 INCHES (457 MM) OF THE
 RELEASE MECHANISM.