| 2022-07-22 13:37:46 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: REVISION #22050030 |
| | 500 N. QUADRILLE BLVD. |
| | BUILDING PERMIT 30 STORY BLDG W/ TWO TOWERS |
| | CONSTRUCTION TYPE: 1A, SPRINKLERED |
| | MIXED OCCUPANCY: B, R-1, R-2, A-2, A4, S-2, M, E |
| | |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | FLORIDA BUILDING CODE,5TH EDITION (2014) |
| | FBC[AMENDED] = 2014 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | |
| | BUILDING REVIEW COMMENTS: |
| | |
| | 1) ON SHEETS A1.225 & A1.228 THE NOTE THAT REFERS TO |
| | ANOTHER SHEET FOR ADDITIONAL POOL INFORMATION DOES NOT |
| | SPECIFY THE SHEET NUMBER TO REFER TO. FBC 107.2.1 |
| | |
| | 2) ON SHEET A2.107 IT APPEARS THAT ONE OF THE LAYERS |
| | WAS NOT TURNED ON. THE RESTROOM FIXTURES, GYM EQUIPMENT |
| | AND FIXTURES IN THE UNITS ARE NOT SHOWN AS THEY WERE IN |
| | THE PREVIOUS VERSION OF THE DRAWING. FBC 107.2.1 |
| | |
| | 3) ON SHEET A2.225 THE DOORS AND SWINGS ARE NOT SHOWN |
| | BUT MAY IMPEDE TRAVEL IN THE CORRIDOR. FBC 1005.7.1 |
| | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED |
| | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY |
| | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE |
| | THAN ONE-HALF. |
| | |
| | 4) SEE FIRE REVIEW COMMENTS FOR DOOR SWINGS IN |
| | DIRECTION OF TRAVEL. 1010.1.2.1 DIRECTION OF SWING. |
| | PIVOT OR SIDE-HINGED SWINGING DOORS SHALL SWING IN THE |
| | DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA |
| | CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS OR A |
| | GROUP H OCCUPANCY. |
| | |
| | 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |