| 2022-12-27 19:13:12 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. FBC R 301, THE STRUCTURAL DETAIL IS TO INCLUDE WIND |
| | DESIGN CRITERIA. CALCULATIONS MAY BE REQUIRED. |
| | |
| | THE DETAIL IS NOT CLEAR - IT STATES THAT THE WALL WILL |
| | BE FILLED WITH "CEMENT". SPECIFY THE "CEMENT" FOR THE |
| | WALL. IT IS NOT CLEAR WHERE CEMENT IS PROPOSED - ENTIRE |
| | WALL? CELLS WITH REBAR? |
| | |
| | SPECIFY CONCRETE STRENGTH FOR THE FOOTING. |
| | |
| | SPECIFY THE SOIL PREP. |
| | |
| | HOW WILL THE CAP BE INSTALLED? |
| | |
| | 2. FBC 107, THERE ARE SEVERAL REFERENCES TO "RETAINING |
| | WALL" - ON THE DETAIL, THE APPLICATION, THE CONTRACT. |
| | AN EMAIL FROM APPLICANT STATED THAT THIS IS NOT A |
| | RETAINING WALL. REMOVE ALL REFERENCES TO "RETAINING". |
| | THE CONTRACT WILL BE REMOVED (DOES NOT NEED TO BE |
| | REVISED), I WILL REDLINE THE APPLICATION. |
| | |
| | 3. FBC 107, THE FOOTING CANNOT ENCROACH THE PROPERTY |
| | LINE. SINCE NO DIMENSIONS WERE PROVIDED, IT IS NOT |
| | CLEAR HOW FAR FROM THE PROPERTY LINE THE FOOTING WILL |
| | BE. ADVISORY, THE PLAN WILL BE REDLINED TO INDICATE |
| | THAT THE FOOTING CANNOT ENCROACH THE PROPERTY LINE. |
| | |
| | 4. FBC 107, INCLUDE THE PRINTED NAME AND SIGNATURE OF |
| | THE INDIVIDUAL TAKING RESPONSIBLITY FOR THE STRUCTURAL |
| | DESIGN. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |