| Plan Review Notes For Permit 22041625 |
| Permit Number |
22041625 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2022-10-11 18:00:13 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | COMMENT FROM PREVIOUS REVIEWS: | | | | | | 1. FBC R 301, PROVIDE A STRUCTURAL DETAIL FOR THE | | | PROPOSED RETAINING WALL AND COLUMNS. THE STRUCTURAL | | | DETAIL IS TO INCLUDE WIND DESIGN CRITERIA. CALCULATIONS | | | MAY BE REQUIRED. | | | | | | 10/11/22 REVIEW: | | | | | | 2. A DETAIL "FREE STANDING WALL DETAILS" WAS SUBMITTED. | | | THE DETAIL SHOWS A PACKED ROCK BASE, ONE BLOCK BELOW | | | GRADE, 6X12X10 BLOCK WALL, 2.5' HIGH. DUE TO THE LACK | | | OF REINFORCING STEEL, A FOUNDATION, AND CONCRETE IT | | | APPEARS THAT THE WALL WILL NOT RESIST WIND LOADS. | | | | | | STRUCTURAL DETAIL IS TO INCLUDE WIND DESIGN CRITERIA. | | | | | | 3. THE PERMIT APPLICATION IS FOR A RETAINING WALL. THE | | | DETAIL SHOWS GRASS AND LEVEL GRADE ON BOTH SIDES. THE | | | PLAN (TOBIAS_SURVEY MARKE UP PAGE.PDF) SHOWS THE POOL | | | DECK AGAINST THE POOL. SINCE IT IS NOT CLEAR WHAT IS | | | BEING PROPOSED, PROVIDE AN ELEVATION OR CROSS SECTION | | | INCLUDING GRADES ON BOTH SIDES OF THE WALL, INCLUDING | | | SHOWING THE WALL RELATIVE TO THE POOL DECK. | | | | | | | | | | | | | | | | | | |
|