2022-07-21 12:17:541. IN ACCORDANCE TO THE DAC ISSUED CONDITION OF
 APPROVAL; LIGHT FIXTURES SHALL BE PULLED AWAY FROM THE
 FACE OF THE CURB FOR CLEARANCE PURPOSES AND SAFETY
 CONCERNS WITH THE OPERATION OF FIRE TRUCKS & OTHER
 LARGE VEHICLES ALONG N RAILROAD AVE. LIGHT FIXTURES ARE
 ALSO TO BE ALIGNED WITH THE STREET TREES PLANTED WITHIN
 LANDSCAPED AREAS ALONG THE ROW.
 - CURRENT DRAWINGS SHOW LIGHT FIXTURES ENCROACHING
 TRAVEL-LANE, STREET DRAINAGE GUTTER, CURB LINES, AND
 OTHER STREETSCAPE ELEMENTS. PLEASE ADJUST ACCORDINGLY.
 - ENGINEERING TYPICALLY REQUIRES A 2-FT. BUFFER OR
 CLEARANCE FROM THE CURB FACE BEFORE ANY LIGHTS, POLE,
 OR STREETSCAPE ELEMENTS CAN BE PLACED WITHIN ROW.
  
 2. MAKE SURE ELECTRIC PLANS ALIGN WITH APPROVED
 ELECTRIC PLANS FOR N RAILROAD AVE. PARKING LOTS AND
 APPROVED STREETSCAPE DESIGN.
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 822-1426 [email protected]