Plan Review Notes
Plan Review Notes For Permit 22041606
Permit Number 22041606
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-05-11 15:00:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE APPLICATION STATES "REPAIRS TO EXISTING
 CONTRACTOR BATHROOM.
  
 THERE IS NO FLOOR PLAN SUBMITTED THAT INDICATES THE
 LOCATION OF THE BATHROOM OR IF THERE IS A UNIT #.
  
 PLEASE ALSO INDICATE WHAT FLOOR THE PROPOSED WORK IS
 ON.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.12.2 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 CONSTRUCTION UNLESS OTHERWISE PERMITTED BY 1.7.11.4.
  
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN
 INDICATING THE LOCATION OF THE BATHROOM. AND A NOTE OF
 ACKNOWLEDGEMENT TO MAINTAIN THE FIRE RATING OF THE
 BATHROOM WALL IF APPLICABLE.
  
  
 2) THE PLAN SHEET SUBMITTAL INDICATES "REMOVE AND
 REPLACE.....TILE FLOORING"
  
 TILE FLOORING COULD HAVE DIFFERENT MEANINGS AND IF NOT
 CERAMIC/PORCELAIN/MARBLE/CEMENT IT CAN BE
 VINYL/LAMINATE ETC AND IS MANUFACTURED FROM AROUND THE
 WORLD AND NOT ALL ARE TESTED AND MEETING LISTED AND
 NFPA STANDARDS.
  
 CERAMIC/PORCELAIN/MARBLE/CEMENT TILE DOES NOT REQUIRE A
 SPEC SHEET.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE SPECIFIC
 TILE TYPE AND/OR PRODUCT SPEC SHEETS OF THE PROPOSED
 FINISHED FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  