| 2022-07-27 08:21:50 | 2ND REVIEW FMC |
| | PERMIT: 22041501 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 01 INDICATES THAT THE MECHANICAL UNITS FOR |
| | THIS 2 STORY 4 UNIT COMMERCIAL APARTMENT BUILDING WILL |
| | BE MINI SPLIT SYSTEMS. SHEET M1 INDICATES THAT EACH |
| | APARTMENT HAS AN AHU AND A CONDENSING UNIT. THE DUCT |
| | WORK APPEARS TO STILL BE IN THE FIRE RATED FLOOR |
| | CEILING ASSEMBLY. THE BATH EXHAUST DUCT ALSO STILL |
| | APPEARS TO BE IN THE RATED FLOOR CEILING ASSEMBLY. |
| | PLEASE ADDRESS 1ST CYCLE COMMENTS AND MAKE SURE THE |
| | DRAWINGS ARE CONSISTENT. |
| | |
| | 2) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS ARE FOR |
| | RESIDENTIAL, THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS SHOULD BE SIZED IN ACCORDANCE TO FEC |
| | C403.2.1. THE CALCULATIONS SHOULD ALSO INCLUDE THE |
| | APARTMENT THAT EACH UNIT IS SIZED TO CONDITION. |
| | |
| | 3) THE COMMON HALL OF THIS COMMERCIAL BUILDING SHOULD |
| | HAVE VENTILATION. PLEASE SHOW THE CALCULATIONS FOR THE |
| | VENTILATION. FMC TABLE 403.3.1.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |