| Date |
Text |
| 2022-07-27 11:53:08 | THE PREVIOUS FAILED FIRE COMMENTS DO NOT SEEM TO BE |
| | ADDRESSED ION THE RESUBMITTAL. |
| | |
| | THE IS A NOTE # 5 ON THE 1ST AND 2ND FLOOR PLANS |
| | STATING NEW FLOORING AND PAINT. |
| | |
| | THERE IS NO INDICATION OF WHAT THAT FLOORING TYPE(S) IS |
| | NOR WHERE IT WILL BE LOCATED. |
| | |
| | PLEASE REVIEW AND ADDRESS THE COMMENTS. |
| | |
| | THE COMMENTS ARE RESUBMITTED BELOW: |
| | |
| | |
| | |
| | ******************************************************* |
| | ************************** |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF NEW FLOORING, BUT NO |
| | INDICATION OF WHAT TYPE OF FLOORING. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TYPE OF |
| | FINISH FLOORING PRODUCT AND PRODUCT NAME AND SPEC SHEET |
| | THAT INDICATES THE FIRE BEHAVIOR RATING. |
| | |
| | FYI.....IF THE PROPOSED IS PORCELAIN OR CERAMIC TILE, |
| | NATURAL STONE TILE, CONCRETE TILES, SPEC SHEETS WOULD |
| | NOT BE REQUIRED. |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |