| 2022-05-20 12:30:04 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22041477 3800 WASHINGTON RD 812 |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | PLUMBING |
| | |
| | 1. PER WPB FBC 107.2.1, PROVIDE A CROSS-SECTION SHOWER |
| | WALL/FLOOR/DRAIN AND THRESHOLD DETAIL SHOWING |
| | COMPLIANCE WITH FBC PL 421.5.2 AS FOLLOWS: |
| | ***A) LINERS SHALL TURN UP ON ALL SIDES NOT LESS THAN 2 |
| | INCHES ABOVE THE FINISHED THRESHOLD LEVEL |
| | ***B) LINERS SHALL BE RECESSED AND FASTENED TO AN |
| | APPROVED BACKING |
| | ***C) LINERS SHALL NOT BE NAILED OR PERFORATED AT ANY |
| | POINT LESS THAN 1 INCH ABOVE THE FINISHED THRESHOLD |
| | ***D) LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL |
| | IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE |
| | SLOPED TOWARD THE FIXTURE DRAIN |
| | ***E) LINERS SHALL BE SECURELY FASTENED TO THE WASTE |
| | OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT |
| | JOINT BETWEEN THE LINER AND THE OUTLET |
| | ***F) FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS |
| | SHALL BE LAID ON, AND SUPPORTED BY, A SMOOTH AND |
| | STRUCTURALLY SOUND BASE. |
| | |
| | 2. PER WPB FBC 107.2.1,SPECIFY LINER MATERIAL COMPLYING |
| | WITH ONE OF THE FOLLOWING FBC PL SECTIONS-421.5.2.1, |
| | 421.5.2.2, 421.5.2.3, 421.5.2.4, 421.5.2.5 OR |
| | 421.5.2.6. NOTE THAT FBC PL 421.5.2.1 PLASTICIZED |
| | POLYVINYL CHLORIDE (PVC) SHEETS MEETING THE |
| | REQUIREMENTS OF ASTM D4551 IS A COMMON LINER USED AND |
| | IS APPROVED. |
| | |
| | 3. FBC PL 421.4.1: WALLS IN SHOWER COMPARTMENTS SHALL |
| | BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND |
| | NONABSORBENT WATERPROOF MATERIALS NOT LESS THAN 6 FEET |
| | ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES |
| | ABOVE THE DRAIN OF THE SHOWER. PER WPB FBC 107.2.1, |
| | PROVIDE A NOTE STATING THE SAME. |
| | |
| | 4. FBC PL 421.4.1 AND 421.5: FLOOR SURFACES SHALL BE |
| | CONSTRUCTED OF IMPERVIOUS, NONCORROSIVE, NONABSORBENT |
| | AND WATERPROOF MATERIALS. PER WPB FBC 107.2.1, PROVIDE |
| | A NOTE STATING THE SAME. |
| | |
| | 5. THE REPLACEMENT OF THE BATHTUB WITH A SHOWER AND THE |
| | REPLACEMENT OF THE SHOWER WITH A BATHTUB REQUIRES NEW |
| | FLOOR PENETRATIONS. PER WPB FBC 107.2.1, PROVIDE |
| | APPLICABLE RATED FLOOR DETAILS FOR PLUMBING |
| | PENETRATIONS COMPLYING WITH THE REQUIREMENTS OF FBC |
| | CHAPTER 7. |
| | |
| | 6. PER WPB FBC 107.2.1, PROVIDE DETAIL OF WATER HEATER |
| | SHOWING HEATER W/STORAGE CAPACITY, PIPING INCLUDING CW, |
| | HW, VALVES (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE |
| | FBC PL 504.2) , THERMAL EXPANSION CONTROL DEVICE |
| | (INCLUDING SIZE), T&P DISCHARGE (INCLUDING TERMINATION) |
| | AND WATER HEATER PAN AND DRAIN (INCLUDING TERMINATION) |
| | PER WPB FPC 107.2.1; COMPLY WITH FBC PL 607.3, 503.1, |
| | 504.1, 504.4, 504.4.1, 504.5, 504.6, 504.7, 504.7.1 AND |
| | 504.7.2. |
| | PLEASE NOTE; PER FBC PL 504.7.2, WHERE A PAN DRAIN WAS |
| | NOT PREVIOUSLY INSTALLED, A PAN DRAIN SHALL NOT BE |
| | REQUIRED FOR A REPLACEMENT WATER HEATER INSTALLATION. |
| | IF THIS IS THE CASE, PER WPB FBC 107.2.1, PLEASE NOTE |
| | ON DETAIL. |
| | |
| | 7.PER WPB FBC 107.2.1 AND FBC PL 409.4, PROVIDE NOTE |
| | STATING "THE WASTE CONNECTION OF A RESIDENTIAL |
| | DISHWASHER SHALL CONNECT DIRECTLY TO A WYE BRANCH |
| | FITTING ON THE TAILPIECE OF THE KITCHEN SINK, DIRECTLY |
| | TO THE DISHWASHER CONNECTION OF A FOOD WASTE DISPOSER, |
| | OR THROUGH AN AIR BREAK TO A STANDPIPE. THE WASTE LINE |
| | OF A RESIDENTIAL DISHWASHER SHALL RISE AND BE SECURELY |
| | FASTENED TO THE UNDERSIDE OF THE SINK RIM OR |
| | COUNTERTOP." |
| | |
| | 8. PER WPB FBC 107.2.1 AND FBC PL 412.3, PROVIDE NOTE |
| | STATING "INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION |
| | VALVES SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR |
| | COMBINATION BALANCED-PRESSURE/THERMOSTATIC VALVES THAT |
| | CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME |
| | A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND |
| | SHALL BE INSTALLED AT THE POINT OF USE. SHOWER AND |
| | TUB-SHOWER COMBINATION VALVES SHALL BE EQUIPPED WITH A |
| | MEANS TO LIMIT THE MAXIMUM SETTING OF THE VALVE TO 120 |
| | DEGREES F, WHICH SHALL BE FIELD ADJUSTED IN ACCORDANCE |
| | WITH THE MANUFACTURER'S INSTRUCTIONS." |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |