Plan Review Notes
Plan Review Notes For Permit 22041477
Permit Number 22041477
Review Stop P
Sequence Number 1
Notes
Date Text
2022-05-20 12:30:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22041477 3800 WASHINGTON RD 812
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 PLUMBING
  
 1. PER WPB FBC 107.2.1, PROVIDE A CROSS-SECTION SHOWER
 WALL/FLOOR/DRAIN AND THRESHOLD DETAIL SHOWING
 COMPLIANCE WITH FBC PL 421.5.2 AS FOLLOWS:
 ***A) LINERS SHALL TURN UP ON ALL SIDES NOT LESS THAN 2
 INCHES ABOVE THE FINISHED THRESHOLD LEVEL
 ***B) LINERS SHALL BE RECESSED AND FASTENED TO AN
 APPROVED BACKING
 ***C) LINERS SHALL NOT BE NAILED OR PERFORATED AT ANY
 POINT LESS THAN 1 INCH ABOVE THE FINISHED THRESHOLD
 ***D) LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL
 IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE
 SLOPED TOWARD THE FIXTURE DRAIN
 ***E) LINERS SHALL BE SECURELY FASTENED TO THE WASTE
 OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT
 JOINT BETWEEN THE LINER AND THE OUTLET
 ***F) FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS
 SHALL BE LAID ON, AND SUPPORTED BY, A SMOOTH AND
 STRUCTURALLY SOUND BASE.
  
 2. PER WPB FBC 107.2.1,SPECIFY LINER MATERIAL COMPLYING
 WITH ONE OF THE FOLLOWING FBC PL SECTIONS-421.5.2.1,
 421.5.2.2, 421.5.2.3, 421.5.2.4, 421.5.2.5 OR
 421.5.2.6. NOTE THAT FBC PL 421.5.2.1 PLASTICIZED
 POLYVINYL CHLORIDE (PVC) SHEETS MEETING THE
 REQUIREMENTS OF ASTM D4551 IS A COMMON LINER USED AND
 IS APPROVED.
  
 3. FBC PL 421.4.1: WALLS IN SHOWER COMPARTMENTS SHALL
 BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND
 NONABSORBENT WATERPROOF MATERIALS NOT LESS THAN 6 FEET
 ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES
 ABOVE THE DRAIN OF THE SHOWER. PER WPB FBC 107.2.1,
 PROVIDE A NOTE STATING THE SAME.
  
 4. FBC PL 421.4.1 AND 421.5: FLOOR SURFACES SHALL BE
 CONSTRUCTED OF IMPERVIOUS, NONCORROSIVE, NONABSORBENT
 AND WATERPROOF MATERIALS. PER WPB FBC 107.2.1, PROVIDE
 A NOTE STATING THE SAME.
  
 5. THE REPLACEMENT OF THE BATHTUB WITH A SHOWER AND THE
 REPLACEMENT OF THE SHOWER WITH A BATHTUB REQUIRES NEW
 FLOOR PENETRATIONS. PER WPB FBC 107.2.1, PROVIDE
 APPLICABLE RATED FLOOR DETAILS FOR PLUMBING
 PENETRATIONS COMPLYING WITH THE REQUIREMENTS OF FBC
 CHAPTER 7.
  
 6. PER WPB FBC 107.2.1, PROVIDE DETAIL OF WATER HEATER
 SHOWING HEATER W/STORAGE CAPACITY, PIPING INCLUDING CW,
 HW, VALVES (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE
 FBC PL 504.2) , THERMAL EXPANSION CONTROL DEVICE
 (INCLUDING SIZE), T&P DISCHARGE (INCLUDING TERMINATION)
 AND WATER HEATER PAN AND DRAIN (INCLUDING TERMINATION)
 PER WPB FPC 107.2.1; COMPLY WITH FBC PL 607.3, 503.1,
 504.1, 504.4, 504.4.1, 504.5, 504.6, 504.7, 504.7.1 AND
 504.7.2.
 PLEASE NOTE; PER FBC PL 504.7.2, WHERE A PAN DRAIN WAS
 NOT PREVIOUSLY INSTALLED, A PAN DRAIN SHALL NOT BE
 REQUIRED FOR A REPLACEMENT WATER HEATER INSTALLATION.
 IF THIS IS THE CASE, PER WPB FBC 107.2.1, PLEASE NOTE
 ON DETAIL.
  
 7.PER WPB FBC 107.2.1 AND FBC PL 409.4, PROVIDE NOTE
 STATING "THE WASTE CONNECTION OF A RESIDENTIAL
 DISHWASHER SHALL CONNECT DIRECTLY TO A WYE BRANCH
 FITTING ON THE TAILPIECE OF THE KITCHEN SINK, DIRECTLY
 TO THE DISHWASHER CONNECTION OF A FOOD WASTE DISPOSER,
 OR THROUGH AN AIR BREAK TO A STANDPIPE. THE WASTE LINE
 OF A RESIDENTIAL DISHWASHER SHALL RISE AND BE SECURELY
 FASTENED TO THE UNDERSIDE OF THE SINK RIM OR
 COUNTERTOP."
  
 8. PER WPB FBC 107.2.1 AND FBC PL 412.3, PROVIDE NOTE
 STATING "INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION
 VALVES SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR
 COMBINATION BALANCED-PRESSURE/THERMOSTATIC VALVES THAT
 CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME
 A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND
 SHALL BE INSTALLED AT THE POINT OF USE. SHOWER AND
 TUB-SHOWER COMBINATION VALVES SHALL BE EQUIPPED WITH A
 MEANS TO LIMIT THE MAXIMUM SETTING OF THE VALVE TO 120
 DEGREES F, WHICH SHALL BE FIELD ADJUSTED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTRUCTIONS."
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  