| 2022-05-12 15:28:29 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22041468 |
| | 5/12/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A-602: SHOW THE CLEAR FLOOR SPACE DIAGRAMS |
| | WITH DIMENSIONS FOR THE PANTRY SINK, DISHWASHER, ICE |
| | MAKER AND REFRIGERATOR- SECS. 606.2, 804.6.1, 804.6.3, |
| | & 804.6.6 FBC ACC. |
| | |
| | 2) P-001 & P-101: A MEANS OF LIMITING THE HOT WATER |
| | DELIVERY TEMPERATURE AT FIXTURES IS REQUIRED AND IT |
| | CANNOT BE A THERMOSTAT ON A WATER HEATER. A MASTER |
| | THERMOSTATIC OR POINT OF USE MIXING VALVE SHALL BE |
| | INSTALLED- SEC. 607.1.1 FBC P. PLEASE DO NOT CONFUSE |
| | THE CODE REQUIREMENT WITH THE TEMPERED WATER DELIVERY |
| | REQUIREMENT FOR PUBLIC LAVATORIES. HOT WATER AT A |
| | MINIMUM OF 110 DEGREES F IS REQUIRED AT THE SINK AND |
| | DISHWASHER- SEC. 607.1. |
| | |
| | 3) P-001: THE FIRESTOPPING DETAIL DOES NOT APPEAR TO BE |
| | A UL TESTED AND APPROVED ASSEMBLY REQUIRED FOR PIPES |
| | PENETRATING THROUGH THE FLOOR SLABS- SECS. 315.1 FBC P |
| | AND 714.4.1.2 FBC B. |
| | |
| | 4) G-900 & P-101: PLEASE SHOW THE WATER SUPPLY PIPING |
| | TO THE DISHWASHER & ICE MAKER- SEC. 602.1 FBC P. |
| | INDICATE HOW DRAINAGE FROM THE UNITS WILL BE DISCHARGED |
| | INDIRECTLY AND CONVEYED TO APPROVED PLACES OF DISPOSAL- |
| | SEC. 802.1 FBC P. |
| | |
| | 5) P-101: PROVIDE BACKFLOW PREVENTERS AT THE INDIVIDUAL |
| | WATER SUPPLY LINES TO THE COFFEE MAKER AND REFRIGERATOR |
| | ICE MAKER- SEC. 608.3 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |