| Date |
Text |
| 2022-05-26 09:42:16 | LECTRIC REVIEW FAILED |
| | 1) RISER DIAGRAM DETAILS #6 CU CONDUCTORS FEEDING |
| | PRIMARY SIDE OF 45 KVA TRANSFORMER. THE PRIMARY CURRENT |
| | FOR A 45KVA TRANSFORMER IS 54 AMPS. THIS LOAD IS |
| | CONSIDERED CONTINUOUS. CONDUCTORS FOR CONTINUOUS LOADS |
| | SHOULD BE SIZED AT 125% OR MINIMUM AMPACITY OF 67.5 |
| | AMPS. NEC TABLE STATES A #4 CU CONDUCTOR TO BE USED. |
| | NEC 110.14(C)(1)(A)(2) AND 215.2(A)(1)(A)] PER TABLE |
| | 310.15(B)(16). |
| | 2) NOMENCLATURE FOR PANEL HV-10 IS DETAILED AS HP-10 ON |
| | PANEL SCHEDULE AND OTHER LOCATIONS. PLEASE CORRECT AS |
| | NEEDED. FBC 107.2 |
| | 3) PLEASE PROVIDE A COMPLETE MECHANICAL EQUIPMENT |
| | SCHEDULE. FBC 107.2 |
| | 4) PLEASE PROVIDE SPECIFICATIONS FOR LIGHTING INVERTER |
| | AND INPUT AND OUTPUT WIRING. FBC 107.2 |
| | 5) PLEASE PROVIDE A LUMINAIR SCHEDULE. FBC 107.2 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |