Plan Review Notes
Plan Review Notes For Permit 22041468
Permit Number 22041468
Review Stop E
Sequence Number 1
Notes
Date Text
2022-05-26 09:42:16LECTRIC REVIEW FAILED
 1) RISER DIAGRAM DETAILS #6 CU CONDUCTORS FEEDING
 PRIMARY SIDE OF 45 KVA TRANSFORMER. THE PRIMARY CURRENT
 FOR A 45KVA TRANSFORMER IS 54 AMPS. THIS LOAD IS
 CONSIDERED CONTINUOUS. CONDUCTORS FOR CONTINUOUS LOADS
 SHOULD BE SIZED AT 125% OR MINIMUM AMPACITY OF 67.5
 AMPS. NEC TABLE STATES A #4 CU CONDUCTOR TO BE USED.
 NEC 110.14(C)(1)(A)(2) AND 215.2(A)(1)(A)] PER TABLE
 310.15(B)(16).
 2) NOMENCLATURE FOR PANEL HV-10 IS DETAILED AS HP-10 ON
 PANEL SCHEDULE AND OTHER LOCATIONS. PLEASE CORRECT AS
 NEEDED. FBC 107.2
 3) PLEASE PROVIDE A COMPLETE MECHANICAL EQUIPMENT
 SCHEDULE. FBC 107.2
 4) PLEASE PROVIDE SPECIFICATIONS FOR LIGHTING INVERTER
 AND INPUT AND OUTPUT WIRING. FBC 107.2
 5) PLEASE PROVIDE A LUMINAIR SCHEDULE. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  