| Plan Review Notes For Permit 22041434 |
| Permit Number |
22041434 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-11 13:36:16 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC R 806.5, PLEASE PROVIDE SPECIFIC DETAILS FOR | | | THE UNVENTED AIR SPACES, AS IT APPEARS THAT ICENYNE IS | | | TO BE USED FOR THE UNDERSIDE OF ROOF SHEATHING | | | INSULATION. PER CODE SECTION FBC R 806.5 THERE ARE | | | SEVERAL OPTIONS TO BE USED DEPENDING ON ALL OF THE | | | PROPOSED AND EXISTING VARIABLES INCLUDING THE AIR | | | PERMIABILITY OF THE INSULATION. | | | | | | 2,) FBC R 311 & R 312, PROVIDE LOCATION AND DETAILS FOR | | | HANDRAILS AND GUARDS ON PLAN SHEETS. | | | | | | 3.) FBC B 107.3.4.1, PLEASE LIST ALL OF THE PROPOSED | | | DEFERRED SUBMITTALS (PRODUCT APPROVALS & SHOP DRAWINGS) | | | ON PLAN SHEETS. PLEASE INCLUDE: HANDRAILS. | | | | | | 4.) FBC B 107.2.1, PLEASE REFER TO THE DRAINAGE PLAN, | | | SITE WALL PERMIT, STORM WATER PREVENTION PLAN, & DEMO | | | PERMIT THAT HAVE BEEN REQUESTED ON BUILDING REVIEW | | | NOTES FOR PERMIT 22041417. THESE ITEMS NEED TO BE | | | APPROVED. | | | | | | | | | |
|