Plan Review Notes
Plan Review Notes For Permit 22041432
Permit Number 22041432
Review Stop B
Sequence Number 1
Notes
Date Text
2022-05-16 11:32:14PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ELEVATION OF THE LOWEST MACHINERY OR EQUIPMENT
 (THE A/C EQUIPMENT) SERVICING THE BUILDING IS SPECIFIED
 AT 15.97 FEET WHICH BELOW THE DESIGN FLOOD ELEVATION OF
 16 FEET NAVD 88. RAISE THE EQUIPMENT SO THAT IT IS AT
 OR ABOVE THE DFE (16 FEET NAVD 88) AND SUBMIT A
 CORRECTED ELEVATION CERTIFICATE. FBC 1612