| 2022-09-26 08:22:02 | 4TH GAS REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC G2415.8.1 - THE CONDUIT FOR THE GAS SLEEVE | | | TO THE FIREPLACE MUST TERMINATE IN AN "OCCUPIABLE | | | PORTION" OF THE BUILDING. BEHIND AN ACCESS PANEL IS NOT | | | "OCCUPIABLE". CONSIDER USING ANOTHER PORTION OF THE | | | BUILDING FOR THE SLEEVE TO ENTER THE STRUCTURE AND THEN | | | CONTINUING OVERHEAD FOR THE REMAINDER OF THE RUN. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] |
|