| 2022-09-01 13:02:34 | 3RD REVIEW FBC-2020 RES. GAS |
| | PERMIT- 22041417 |
| | 9/1/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P-1 & P-4: THE TRACPIPE CSST PS-II |
| | PRE-SLEEVED GAS PIPING IS APPROVED FOR |
| | UNDERGOUND/UNDERSLAB INSTALLATION, HOWEVER THE SLEEVED |
| | PIPE AND VENT PORT SHALL TERMINATE IN OCCUPIABLE |
| | PORTIONS OF THE BUILDING PER SEC. G2415.8.1 FBC RES |
| | (404.14.1 FBC FG). THE SLEEVE SHALL EXTEND A MINIMUM OF |
| | 2-INCHES INTO THE SPACE. THE RESUBMITTED PLAN APPEARS |
| | TO SHOW THE TERMINATIONS INSIDE THE WALLS ADJACENT TO |
| | THE FIREPLACE AND THE RANGE. |
| | |
| | A) PLEASE NOTE THAT THE AC CLOSET ADJACENT TO THE |
| | FIREPLACE CANNOT BE THE OCCUPIABLE SPACE FOR |
| | TERMINATION BECAUSE IT IS A PLENUM CLOSET- SEC. G2415.3 |
| | FBC RES (404.3 FBC FG). |
| | |
| | B) CONCERNING THE RANGE, THE SLEEVED TRACPIPE SHALL |
| | TERMINATE MINIMUM 2-INCHES ABOVE THE FLOOR BEHIND THE |
| | RANGE OR IN AN ADJACENT CABINET. PLEASE NOTE A FLEXIBLE |
| | CONNECTOR IS REQUIRED FOR THE RANGE. |
| | |
| | 2) M-1: IN RESPONSE TO COMMENT #8 FROM THE 1ST GAS |
| | REVIEW, THE ENGINEER IS SPECIFYING A TYPE B FLUE VENT |
| | SYSTEM WHICH IS NOT APPROVED FOR USE BY THE |
| | MANUFACTURER- SEC. G2427.2.1 FBC RES. PLEASE SEE PAGE |
| | 21 OF THE CRAVE 4836 HEATILATOR INSTALLATION MANUAL FOR |
| | APPROVED FLUE VENT- HEARTH & HOME TECHNOLOGIES DVP |
| | VENTING SYSTEMS. PLEASE NOTE B VENTS ARE TYPICALLY USED |
| | FOR NATURAL DRAFT APPLIANCES- SEE TABLE G2427.4 FBC |
| | RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |