Plan Review Notes
Plan Review Notes For Permit 22041417
Permit Number 22041417
Review Stop M
Sequence Number 2
Notes
Date Text
2022-07-14 08:05:462ND REVIEW FMC
 PERMIT: 22041417
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGY CALCULATIONS SUBMITTED THIS CYCLE SHOWS
 ON PAGE 2 THAT THERE ARE 3 AHU?S FOR THE HOUSE AND THE
 COTTAGE. AHU-1 IS FOR 1166 SQUARE FEET AND CONDITIONS
 THE LIVING-DINING. AHU-2 IS FOR 1102 SQUARE FEET AND
 CONDITIONS THE MASTER-KITCHEN. AHU-3 IS FOR 300 SQUARE
 FEET AND CONDITIONS THE COTTAGE. NOTHING ON PAGE 2 OF
 THE ENERGY CALCULATIONS INDICATES THE GARAGE AS BEING
 CONDITIONED. THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS SPECIFIES 5 UNITS FOR THE PROJECT WHICH
 INCLUDES THE HOUSE, GARAGE AND CABANA. THE AHU?S LISTED
 ON THE EQUIPMENT SIZING CALCULATIONS ARE- AHU-1, AHU-2,
 AHU-3, AHU-4 AND AHU-5. SHEET M-1 AND M-2 LISTS AHU-1A,
 AHU-B, AHU-2A, AHU-2B AND AHU-3
 PLEASE PROVIDE DOCUMENTS THAT ARE CONSISTENT WITH EACH
 OTHER. PLEASE ALSO PROVIDE AN ENERGY CALCULATIONS THAT
 SHOWS THE MECHANICAL SYSTEMS CONSISTENT WITH THE
 MECHANICAL SIZING CALCULATIONS AND THE MECHANICAL
 DRAWINGS.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  