| | 2ND REVIEW FBC-2020 RES. GAS |
| | PERMIT- 22041417 |
| | 7/14/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. THERE WERE NO CORRECTIONS |
| | TO THE PLANS OR RESPONSES PROVIDED TO ADDRESS THE 1ST |
| | REVIEW COMMENTS PRINTED BELOW. PLEASE COMPLY WITH THE |
| | COMMENTS. PLEASE NOTE THAT GAS CAN BE UNDER A SEPARATE |
| | PERMIT IF REQUESTED. |
| | |
| | 1) SHEETS P1 & P4: NOTE 9 ON P1 INDICATES A 2 PSI |
| | REGULATOR, THE RISER ON P4 SHOWS A 0.5 PSI REGULATOR- |
| | WHICH IS IT? |
| | |
| | 2) P1 & P4: PIPING TO THE GAS DRYER NOT SHOWN- SEC. |
| | G413.1 FBC RES. |
| | |
| | 3) P1, P2, P4: REFER TO SECS. G2411.1 & G2411.2- |
| | G2411.3 AND PROVIDE ELECTRICAL BONDING DETAILS AND |
| | NOTES FOR THE METALLIC AND CSST PIPING. |
| | |
| | 4) P1 & P3: PER NOTE #18 PLEASE REFER TO SEC. G2415.14 |
| | AND INDICATE THE TYPE AND SIZE OF FACTORY SLEEVE AND |
| | SUBMIT SPECIFICATIONS FOR THE SLEEVE TO VERIFY LISTING |
| | COMPLIANCE. PLEASE NOTE THAT COMPLETE INSTALLATION |
| | GUIDELINES FOR THE CSST PIPING SHALL BE SUBMITTED FOR |
| | REVIEW, OR CAN BE A DEFERRED SUBMITTAL- SEC. G2425.5.4 |
| | FBC RES AND 107.3.4.1 WPB. |
| | |
| | 5) P1 & P3: PER NOTE #18 PROVIDE A VENT PORT DETAIL FOR |
| | THE CSST SLEEVES AND INDICATE HOW THE SLEEVES WILL BE |
| | SEALED AT THE TERMINATION LOCATIONS INSIDE THE |
| | BUILDING- SEC. G2415.8.1 FBC RES. |
| | |
| | 6) P1 & P3: PROVIDE TANKLESS WATER HEATER CONDENSATE |
| | DISPOSAL PLANS INCLUDING INSTALLATION OF THE |
| | MANUFACTURER'S RECOMMENDED NEUTRALIZING DEVICE PER SEC. |
| | G2408.1 FBC RES. INCLUDE THE SPECS FOR THE DEVICES IN |
| | THE EQUIPMENT SCHEDULE AND MODIFY THE DRAWINGS TO SHOW |
| | TYPE AND SIZE OF PIPING, PIPING RUN AND DISCHARGE |
| | LOCATIONS- SECS. 307.2-307.3 FBC FG. |
| | |
| | 7) P1 & P3: SHOW THE REQUIRED INSTALLATION CLEARANCES |
| | FOR THE GAS WATER HEATERS- SECS. G2427.1 & G2448.1 FBC |
| | RES. |
| | |
| | 7) P1 & P4 GAS RANGE: SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE NEW RANGE THAT SHOW THE BTU GAS |
| | LOAD, INPUT PRESSURE, AND LISTING OF THE APPLIANCE- |
| | SEC. G2447.1 FBC RES. A) PROVIDE COMBUSTION AIR |
| | CALCULATIONS FOR THE RANGE- SEC. G2407.1 FBC RES. |
| | |
| | 8) P1 & P4 GAS FIREPLACE: PROVIDE A DIRECT VENTING |
| | DIAGRAM SHOWING THE TYPES AND SIZES OF AIR INLET AND |
| | EXHAUST VENT DUCTS, DUCT RUNS AND TERMINATION |
| | LOCATIONS- SEC. SUBMIT SPECS FOR THE VENT DUCTS- |
| | G2427.2.1 & G2427.8 ITEM #3 FBC RES. |
| | |
| | 9) P1 & P4 BBQ: SUBMIT COMPLETE SPECIFICATIONS AND |
| | INSTALLATION MANUAL FOR THE BBQ GRILL- G2448.1 FBC RES. |
| | THE SPECS SHALL SHOW THE BTU LOAD, GAS INPUT PRESSURE, |
| | CLEARANCES TO COMBUSTIBLE AND OVERHEAD CONSTRUCTION, |
| | COMBUSTION AIR AND VENTILATION, AND EXHAUST VENTING |
| | GUIDELINES. PLEASE NOTE THAT AN EXHAUST HOOD AND DUCT |
| | SYSTEM MAY BE REQUIRED- SEC. G2448.1 FBC RES. PROVIDE |
| | PLAN DETAILS THAT REFLECT THE INSTALL MANUAL |
| | RECOMMENDATIONS AND RESTRICTIONS. A) SHOW THE CLEARANCE |
| | DISTANCES FROM THE GRILL EXHAUST TO GRAVITY AND |
| | MECHANICAL AIR INTAKES INTO THE BUILDING- SEC. R303.5.1 |
| | FBC RES. MINIMUM 10 FT. CLEARANCES REQUIRED. |
| | |
| | 10) P1 &P4 GAS DRYER: THE GAS DRYER SUBMITTAL IS |
| | INCOMPLETE. PROVIDE COMPLETE SPECIFICATIONS AND |
| | INSTALLATION GUIDELINES- G2438.1 FBC RES. THE SPECS |
| | SHALL SHOW THE BTU LOAD, INPUT PRESSURE AND SHOW |
| | GUIDELINES FOR COMBUSTION AIR, MAKEUP, AND EXHAUST |
| | VENTING. PROVIDE DETAILS ON THE PLAN IN ACCORDANCE WITH |
| | THE SPECS AND SEC. G2439.1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |