| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | 1.) FBC R 806.5, PLEASE PROVIDE SPECIFIC DETAILS FOR |
| | THE UNVENTED AIR SPACES, AS IT APPEARS THAT ICENYNE IS |
| | TO BE USED FOR THE UNDERSIDE OF ROOF SHEATHING |
| | INSULATION. PER CODE SECTION FBC R 806.5 THERE ARE |
| | SEVERAL OPTIONS TO BE USED DEPENDING ON ALL OF THE |
| | PROPOSED AND EXISTING VARIABLES INCLUDING THE AIR |
| | PERMIABILITY OF THE INSULATION. |
| | 2.) FBC B 107.2.1, PLEASE PROVIDE A DRAINAGE PLAN FOR |
| | THE SITE. |
| | 3.) FBC B 107.2.1, PROVIDE CONFIRMATION OF A SITE WALL |
| | PERMIT. |
| | 4.) FBC B 107.2.1, PROVIDE DETAILS FOR A STORM WATER |
| | PREVENTION PLAN DURING CONSTRUCTION. |
| | 5.) FBC B 107.2.1, PROVIDE CONFIRMATION IF ONE OF THE |
| | APPROVED ROLL OFF/FRANCHISE HAULERS WILL BE USED FOR |
| | REMOVAL OF DEBRIS. |
| | 6.) FBC B 107.2.1, IT APPEARS THAT THERE IS AN EXISTING |
| | ONE STORY BUILDING AND EXTERIOR SECTIONS OF OTHER |
| | STRUCTURES THAT ARE TO BE DEMILISHED. IF THIS IS |
| | ACCURATE, PROVIDE CONFIRMATION OF A DEMO PERMIT. |
| | 7.) FBC R 311 & R 312, PROVIDE LOCATION AND DETAILS FOR |
| | HANDRAILS AND GUARDS ON PLAN SHEETS. |
| | 8.) FBC B 107.3.4.1, PLEASE LIST ALL OF THE PROPOSED |
| | DEFERRED SUBMITTALS(PRODUCT APPROVALS & SHOP DRAWINGS) |
| | ON PLAN SHEETS. PLEASE INCLUDE: HANDRAILS, & PERGOLA. |
| | |
| | |