| Notes |
| Date |
Text |
| 2022-05-16 13:05:12 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 22041384 | | | 5/16/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS P-002 & P-412: EWH-2 SHOWN IN RESTROOM DETAIL | | | 1 HAS BEEN REMOVED FROM THE EQUIPMENT SCHEDULE- SEC. | | | 107.2.1 WPB. | | | | | | 2) P-602: SANITARY FIXTURE AND BRANCH DRAIN PIPINGS FOR | | | THE NEW HD AND FD-2 NOT SHOWN IN THE ISOMETRIC DRAWING- | | | SEC. 107.2.1 WPB. | | | | | | 3) P-602: PLEASE CLARIFY WHY THE FLOOR DRAINS WERE | | | CHANGED TO HUB DRAINS.- SEC. 107.2.1 WPB. WERE THE TRAP | | | PRIMERS REQUIRED FOR EMERGENCY FLOOR DRAINS STILL TO BE | | | USED OR REMOVED?- THEY ARE REQUIRED- SEC. 1002.4.1 FBC | | | P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|