Plan Review Notes
Plan Review Notes For Permit 22041318
Permit Number 22041318
Review Stop Z
Sequence Number 3
Notes
Date Text
2022-08-23 11:47:54FAILED
  
 1) UPDATED COMMENT: THANK YOU FOR PROVIDING SHEET
 ASK-01 SHOWING THE PROPOSED NEW GENERATOR, THE NEW
 CU-1, THE RELOCATED DUMPSTER AND THE EXPANDED SCREENING
 ENCLOSURE.
  
 A. THE PLANS SHOW THE EXISTING LOADING ZONE, WHICH IS
 CODE REQUIRED TO BE A MINIMUM OF 50 FEET LONG, REDUCED
 TO 30 FEET IN LENGTH, WHICH IS NOT PERMITTED UNLESS THE
 LOADING ZONE IS REPLACED AT AN ALTERNATIVE LOCATION.
 THE ALTERNATIVE LOCATION MUST BE DESIGNATED, INCLUDING
 ANY NECESSARY PERMITS TO INSTALL, PRIOR TO THIS PERMIT
 BEING APPROVED BY ZONING.
  
 B. THE CITY EXPRESSLY PROHIBITS CHAIN LINK FENCES WITH
 SLATS FOR SCREENING, SO AN ALTERNATIVE FENCE MATERIAL
 SHALL BE USED. THE SCREENING FENCE WILL REQUIRE A
 SEPARATE PERMIT.
  
 C. THE RECONFIGURATION OF THE GROUND LEVEL OF THE SITE,
 IF THE LOADING ZONE COMMENT CAN BE ADDRESSED, REQUIRES
 THE APPROVAL OF A MINOR PLANNED DEVELOPMENT AMENDMENT.
 THE MINOR PLANNED DEVELOPMENT AMENDMENT APPLICATION IS
 SUBMITTED TO THE CITY'S PLANNING DIVISION.
  
 D. THE PALM BEACH COUNTY PROPERTY APPRAISER SHOWS THAT
 THE PROPOSED LOCATION OF THE NEW CU-1 AND POSSIBLY THE
 NEW GENERATOR ARE NOT ON THE SAME PARCEL AS THE
 BUILDING HOUSING THE BUILDING THAT THE NEW ESPN
 LOCATION WILL BE IN, SO THESE FACILITIES NEED TO BE
 ACCURATELY REFLECTED ON PERMITS TIED TO THE PARCEL THEY
 ARE LOCATED ON. THE PARCELS ARE IN TWO DIFFERING LLC
 OWNERSHIP.
  
 E. A RECENT SURVEY SHOWING THE AREA IS REQUIRED SO THAT
 STAFF CAN VERIFY THE EXISTING CONDITIONS AND HOW THE
 PROPOSED CHANGES AFFECT THE AREA.
  
 2) THE SATELLITE DISH WILL BE REVIEWED AS A SEPARATE
 PERMIT UPON APPROVAL OF A WIRELESS COMMUNICATION
 FACILITY PERMIT APPLICATION.
  