| 2022-08-23 11:47:54 | FAILED |
| | |
| | 1) UPDATED COMMENT: THANK YOU FOR PROVIDING SHEET |
| | ASK-01 SHOWING THE PROPOSED NEW GENERATOR, THE NEW |
| | CU-1, THE RELOCATED DUMPSTER AND THE EXPANDED SCREENING |
| | ENCLOSURE. |
| | |
| | A. THE PLANS SHOW THE EXISTING LOADING ZONE, WHICH IS |
| | CODE REQUIRED TO BE A MINIMUM OF 50 FEET LONG, REDUCED |
| | TO 30 FEET IN LENGTH, WHICH IS NOT PERMITTED UNLESS THE |
| | LOADING ZONE IS REPLACED AT AN ALTERNATIVE LOCATION. |
| | THE ALTERNATIVE LOCATION MUST BE DESIGNATED, INCLUDING |
| | ANY NECESSARY PERMITS TO INSTALL, PRIOR TO THIS PERMIT |
| | BEING APPROVED BY ZONING. |
| | |
| | B. THE CITY EXPRESSLY PROHIBITS CHAIN LINK FENCES WITH |
| | SLATS FOR SCREENING, SO AN ALTERNATIVE FENCE MATERIAL |
| | SHALL BE USED. THE SCREENING FENCE WILL REQUIRE A |
| | SEPARATE PERMIT. |
| | |
| | C. THE RECONFIGURATION OF THE GROUND LEVEL OF THE SITE, |
| | IF THE LOADING ZONE COMMENT CAN BE ADDRESSED, REQUIRES |
| | THE APPROVAL OF A MINOR PLANNED DEVELOPMENT AMENDMENT. |
| | THE MINOR PLANNED DEVELOPMENT AMENDMENT APPLICATION IS |
| | SUBMITTED TO THE CITY'S PLANNING DIVISION. |
| | |
| | D. THE PALM BEACH COUNTY PROPERTY APPRAISER SHOWS THAT |
| | THE PROPOSED LOCATION OF THE NEW CU-1 AND POSSIBLY THE |
| | NEW GENERATOR ARE NOT ON THE SAME PARCEL AS THE |
| | BUILDING HOUSING THE BUILDING THAT THE NEW ESPN |
| | LOCATION WILL BE IN, SO THESE FACILITIES NEED TO BE |
| | ACCURATELY REFLECTED ON PERMITS TIED TO THE PARCEL THEY |
| | ARE LOCATED ON. THE PARCELS ARE IN TWO DIFFERING LLC |
| | OWNERSHIP. |
| | |
| | E. A RECENT SURVEY SHOWING THE AREA IS REQUIRED SO THAT |
| | STAFF CAN VERIFY THE EXISTING CONDITIONS AND HOW THE |
| | PROPOSED CHANGES AFFECT THE AREA. |
| | |
| | 2) THE SATELLITE DISH WILL BE REVIEWED AS A SEPARATE |
| | PERMIT UPON APPROVAL OF A WIRELESS COMMUNICATION |
| | FACILITY PERMIT APPLICATION. |
| | |