2022-07-07 18:40:49FAILED
  
 NO UPDATED PLANS PROVIDED SO ORIGINAL COMMENTS STILL
 APPLY. PERMIT 21100781 REFERENCED IN THE RESPONSE DOES
 NOT SHOW ANY GROUND MOUNTED EQUIPMENT.
  
 1) SHEETS E-101, M-202, AND M-301 SHOW CU-1A ON THE
 GROUND FLOOR, WHICH REQUIRES ADDITIONAL INFORMATION ON
 HOW THIS WILL BE SCREENED IN ACCORDANCE WITH THE
 CITYPLACE DRI MECHANICAL EQUIPMENT SCREENING
 REQUIREMENTS. ADDITIONALLY, THE CU-1A 3P-F20SS APPEARS
 TO BE MOUNTED TO THE EXTERIOR WALL AND NEEDS TO SHOW
 HOW IT IS SCREENED. ON THE APPROVED PLANS, THESE ARE
 SHOWN ON THE ROOF, SCREENED.
  
 2) THE SATELLITE DISH WILL NEED TO MEET THE MECHANICAL
 EQUIPMENT SCREENING REQUIREMENTS.
  