| 2022-05-17 06:49:25 | 1ST REVIEW FMC | | | PERMIT: 22041318 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-401: THE CU-1A WAS CHANGED FROM AN 8 TON | | | UNIT TO A 10 TON UNIT. THE CHILLED WATER FAN COIL | | | SCHEDULE ALSO SHOWS THAT SEVERAL UNITS HAVE A LARGER | | | GPM RATES. PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR THIS ADDITIONAL LOAD. FEC C403.7.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|