| Plan Review Notes For Permit 22041267 |
| Permit Number |
22041267 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-05 13:12:59 | 1ST REVIEW FMC | | | PERMIT: 22041267 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE GUEST | | | HOUSE. FEC 101.5.1.1.2 | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FEC R403.7.1 | | | | | | 3) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE | | | INDOOR UNITS, THE LOCATION OF THE CONDENSING UNITS, THE | | | ANCHORAGE OF THE OUTDOOR UNITS AND THE CONDENSATE | | | PIPING WITH THE CONDENSATE DISPOSAL LOCATION. FBC | | | 107.2.1 | | | | | | 4) THE DESIGNER OF THE DRAWINGS MUST PRINT AND SIGN | | | THEIR NAMES ON EACH SHEET. FS 471/481 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|