Plan Review Notes
Plan Review Notes For Permit 22041254
Permit Number 22041254
Review Stop E
Sequence Number 3
Notes
Date Text
2022-09-16 09:08:33FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 RISER SHOWS 200A SERVICE LOAD CALCULATION SHOWS 227
 AMPS. SEE ARTICLE 220 FOR SERVICE CALCULATIONS.
  
 CARE CHARGER IS TO SIZED PER 625.41.