| Plan Review Notes For Permit 22041254 |
| Permit Number |
22041254 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-09-16 09:08:33 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | RISER SHOWS 200A SERVICE LOAD CALCULATION SHOWS 227 | | | AMPS. SEE ARTICLE 220 FOR SERVICE CALCULATIONS. | | | | | | CARE CHARGER IS TO SIZED PER 625.41. |
|