2022-04-27 19:05:4404/27/22 1ST PLUMBING BACKFLOW REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A GENERAL CONTRACTOR OR AN UNDERGROUND UTILITY AND
 EXCAVATION CONTRACTOR CANNOT INSTALL A BACKFLOW DEVICE
 PER THE 2020 FLORIDA STATUTES TITLE XXXII CHAPTER
 489.105(N). PLEASE PROVIDE THE PERMITTING DEPARTMENT
 WITH A VALID STATE OF FLORIDA LICENSED CONTRACTOR ALONG
 WITH AN APPLICATION.
  
 FS 489.105 DEFINITIONS.-- AS USED IN THIS PART:
 (1) "BOARD" MEANS THE CONSTRUCTION INDUSTRY LICENSING
 BOARD.
 (2) "DEPARTMENT" MEANS THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION.
 (3) "CONTRACTOR" MEANS THE PERSON WHO IS QUALIFIED FOR,
 AND IS ONLY RESPONSIBLE FOR, THE PROJECT.
  
 (N) "UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR"
 MEANS A CONTRACTOR WHOSE SERVICES ARE LIMITED TO THE
 CONSTRUCTION, INSTALLATION, AND REPAIR, ON PUBLIC OR
 PRIVATE PROPERTY, WHETHER ACCOMPLISHED THROUGH OPEN
 EXCAVATIONS OR THROUGH OTHER MEANS, INCLUDING, BUT NOT
 LIMITED TO, DIRECTIONAL DRILLING, AUGER BORING, JACKING
 AND BORING, TRENCHLESS TECHNOLOGIES, WET AND DRY TAPS,
 GROUTING, AND SLIP LINING, OF MAIN SANITARY SEWER
 COLLECTION SYSTEMS, MAIN WATER DISTRIBUTION SYSTEMS,
 STORM SEWER COLLECTION SYSTEMS, AND THE CONTINUATION OF
 UTILITY LINES FROM THE MAIN SYSTEMS TO A POINT OF
 TERMINATION UP TO AND INCLUDING THE METER LOCATION FOR
 THE INDIVIDUAL OCCUPANCY, SEWER COLLECTION SYSTEMS AT
 PROPERTY LINE ON RESIDENTIAL OR SINGLE-OCCUPANCY
 COMMERCIAL PROPERTIES, OR ON MULTIOCCUPANCY PROPERTIES
 AT MANHOLE OR WYE LATERAL EXTENDED TO AN INVERT
 ELEVATION AS ENGINEERED TO ACCOMMODATE FUTURE BUILDING
 SEWERS, WATER DISTRIBUTION SYSTEMS, OR STORM SEWER
 COLLECTION SYSTEMS AT STORM SEWER STRUCTURES. HOWEVER,
 AN UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR MAY
 INSTALL EMPTY UNDERGROUND CONDUITS IN RIGHTS-OF-WAY,
 EASEMENTS, PLATTED RIGHTS-OF-WAY IN NEW SITE
 DEVELOPMENT, AND SLEEVES FOR PARKING LOT CROSSINGS NO
 SMALLER THAN 2 INCHES IN DIAMETER IF EACH CONDUIT
 SYSTEM INSTALLED IS DESIGNED BY A LICENSED PROFESSIONAL
 ENGINEER OR AN AUTHORIZED EMPLOYEE OF A MUNICIPALITY,
 COUNTY, OR PUBLIC UTILITY AND THE INSTALLATION OF SUCH
 CONDUIT DOES NOT INCLUDE INSTALLATION OF ANY CONDUCTOR
 WIRING OR CONNECTION TO AN ENERGIZED ELECTRICAL SYSTEM.
 AN UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR MAY
 NOT INSTALL PIPING THAT IS AN INTEGRAL PART OF A FIRE
 PROTECTION SYSTEM AS DEFINED IN S. 633.102 BEGINNING AT
 THE POINT WHERE THE PIPING IS USED EXCLUSIVELY FOR SUCH
 A SYSTEM.
  
 PLEASE PROVIDE A SEPARATE PERMIT, ONE FOR FIRE WITH A
 FIRE SPRINKER CONTRACTOR OR AN I/II/OR IV LICENSE AND
 THE OTHER FOR DOMESTIC BACKFLOW FROM A PLUMBING
 CONTRACTOR AS MENTIONED BELOW;
  
 2. THE FIRE SPRINKLER SYSTEM REQUIRES A DOUBLE CHECK
 DETECTOR ASSEMBLY INSTALLED BY A LICENSED CONTRACTOR
 PER THE 2020 FLORIDA STATUTES 633.102, INSURANCE,
 CHAPTER 633, FIRE PREVENTION AND CONTROL, 3 (A)
 CONTRACTOR I, II, AND V ARE THE ONLY ONE'S LICENSED
 CONTRACTOR WHOSE BUSINESS INCLUDES THE EXECUTION OF
 CONTRACTS REQUIRING THE ABILITY TO LAYOUT, FABRICATE,
 INSTALL, INSPECT, ALTER, REPAIR, AND SERVICE ALL TYPES
 OF FIRE PROTECTION SYSTEMS, EXCLUDING PRE-ENGINEERED
 SYSTEMS AND THIS NEEDS TO BE CERTIFIED BY THE UTILITIES
 DEPARTMENT. THESE ARE CONTAINMENT DEVICES AS THE CITY
 OF WEST PALM BEACH UTILITIES DEPARTMENT HAS
 JURISDICTION OVER THEM AND NEEDS TO BE CERTIFIED.
  
 3. YOU WILL REQUIRE TWO SEPARATE APPLICATIONS, ONE FOR
 THE FIRE AND SPECIFICATION OF A DUAL DOUBLE DETECTOR
 VALVE AND THE OTHER FOR ANY REDUCED PRINCIPAL VACUUM
 BREAKER WITH THE SPECIFICATION.
  
 4. ALL BACKFLOW DEVICES MUST BE LEAD-FREE. LEAD-FREE
 (LF) SHALL BE INCLUDED IN THE SERIAL NUMBER OR STAMPED
 ON THE BODY OF THE DEVICE. ANY DEVICE THAT HAS BEEN
 ALTERED AFTER BEING ASSEMBLED BY THE MANUFACTURER WILL
 NOT BE APPROVED.
  
 5. A SITE PLAN DEPICTING THE PROPOSED BACKFLOW
 PREVENTION DEVICE'S GENERAL LOCATION CAN BE DONE BY
 GOING TO THE PROPERTY APPRAISER WEBSITE, PRINTING OUT A
 STRUCTURAL LAYOUT OF THE BUILDING, AND HAND DRAWING THE
 METER LOCATION WITH THE BACKFLOW.
  
 6. ONE COPY OF THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE DEVICE'S MAKE, MODEL, AND
 SIZE SHALL BE LISTED IN THE DESCRIPTION OF THE WORK
 SECTION ON THE PERMIT APPLICATION.
  
 7. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE
 WHICH CONTAINS NOT MORE THAN 0.25-PERCENT LEAD.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  