| 2022-12-20 14:38:51 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THERE IS NOT ANY INSULATION SPECIFIED FOR UNDER THE | | | RAISED FLOOR OF THE ADDITION. SPECIFY THE UNDER FLOOR | | | INSULATION ON THE PLANS. FBC ENERGY CONSERVATION | | | R402.2.8 | | | | | | 2) THERE IS NOT ANY INSULATION SPECIFIED FOR THE | | | ROOF/CEILING SPACE OF THE ADDITION. SPECIFY THE | | | ROOF/CEILING INSULATION ON THE PLANS. FBC ENERGY | | | CONSERVATION R402.2.2 | | | | | | 3) SUBMIT ENERGY CALCULATIONS FOR THE NEW ADDITION. FBC | | | ENERGY CONSERVATION CHAPTER 4 | | | | | | 4) THE PRODUCT APPROVALS FOR THE FRENCH DOORS AND THE | | | WINDOW MULLIONS ARE NOT APPROVED IN WRITING BY THE | | | ARCHITECT. FBC 107.3.4 | | | | | | 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | | | | | | | | | | | | | |
|