2022-12-20 14:38:51PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE IS NOT ANY INSULATION SPECIFIED FOR UNDER THE
 RAISED FLOOR OF THE ADDITION. SPECIFY THE UNDER FLOOR
 INSULATION ON THE PLANS. FBC ENERGY CONSERVATION
 R402.2.8
  
 2) THERE IS NOT ANY INSULATION SPECIFIED FOR THE
 ROOF/CEILING SPACE OF THE ADDITION. SPECIFY THE
 ROOF/CEILING INSULATION ON THE PLANS. FBC ENERGY
 CONSERVATION R402.2.2
  
 3) SUBMIT ENERGY CALCULATIONS FOR THE NEW ADDITION. FBC
 ENERGY CONSERVATION CHAPTER 4
  
 4) THE PRODUCT APPROVALS FOR THE FRENCH DOORS AND THE
 WINDOW MULLIONS ARE NOT APPROVED IN WRITING BY THE
 ARCHITECT. FBC 107.3.4
  
 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  