| 2023-02-24 07:44:15 | 2ND PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | PREVIOUS COMMENTS NOT ADDRESSED AND CHANGES NOT MADE |
| | |
| | 1. 2020 FPC 912.1 - THERE IS ONE BATHROOM GROUP AT THE |
| | TOP OF THE PAGE AND ONE ON THE BOTTOM LEFT OF THE PAGE |
| | THAT IS NOT VENTED TO CODE. THE SHOWER AND WATER CLOSET |
| | ARE BOTH ON THE HIGH SIDE OF THE VENTED FIXTURE |
| | CONNECTION AND ARE NOT ALLOWED TO BE. ONLY ONE WET |
| | VENTED FIXTURE IS ALLOWED ON THE HIGH SIDE OF THE |
| | VENTED FIXTURE CONNECTION. EITHER CHANGE THE VENTING |
| | METHOD FROM WET VENT TO ANOTHER METHOD OR RECONFIGURE |
| | THE CONNECTIONS. THERE ARE SEVERAL BRANCHES THAT ARE |
| | NON-COMPLIANT. "SINKS" CANNOT WET VENT BATHROOM GROUP |
| | FIXTURES, ONLY "OTHER BATHROOM GROUP FIXTURES" CAN LIKE |
| | LAVATORIES. |
| | |
| | PLEASE RECONFIGURE THE ISORMETRIC DRAWING TO ADDRESS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |