| 2023-03-10 12:27:31 | ELECTRIC REVIEW FAILED |
| | |
| | 1) PLEASE PROVIDE A COMPLETE RISER DIAGRAM. INCLUDE ALL |
| | EQUIPMENT, CONDUIT, WIREWAY, CONDUCTOR, SIZES AND |
| | NUMBER OF CONDUCTORS IN ALL RACE WAYS AND WIREWAYS. NEC |
| | 215.5 |
| | |
| | NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE |
| | AUTHORITY HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER |
| | DETAILS SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF |
| | THE FEEDERS. |
| | |
| | 2 ) IT APPEARS THERE ARE MULTIPLE CONDUCTORS IN |
| | CONDUITS BETWEEN WIREWAYS THAT WILL NEED TO BE DE RATED |
| | AS REQUIRED PER NEC 310.15(B)(3). |
| | |
| | 310.15(B)(3). ADJUSTMENT FACTORS. MORE THAN THREE |
| | CURRENT-CARRYING CONDUCTORS. WHERE THE NUMBER OF |
| | CURRENT-CARRYING CONDUCTORS IN A RACEWAY OR CABLE |
| | EXCEEDS THREE, OR WHERE SINGLE CONDUCTORS OR |
| | MULTICONDUCTOR CABLES ARE INSTALLED WITHOUT MAINTAINING |
| | SPACING FOR A CONTINUOUS LENGTH LONGER THAN 600 MM (24 |
| | IN.) AND ARE NOT INSTALLED IN RACEWAYS, THE ALLOWABLE |
| | AMPACITY OF EACH CONDUCTOR SHALL BE REDUCED AS SHOWN IN |
| | TABLE 310.15(B)(3)(A) |
| | |
| | 3) PLEASE RESPOND TO PREVIOUS COMMENT. THE EXISTING |
| | ELECTRICAL SERVICE WAS PERMITTED AS 300-AMP. YOU DETAIL |
| | THE EXISTING SERVICE AS 400 AMP. PLEASE RESOLVE THIS |
| | CONFLICT. FBC 107.2 |
| | |
| | FBC 107.2 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. |
| | |
| | 4) PLEASE DETAIL ELECTRIC WORK THAT IS EXISTING AND TO |
| | REMAIN AND WORK THAT IS NEW AND TO BE ADDED ON ALL |
| | ELECTRIC PLANS. FBC 107.2 |
| | |
| | 5) PLEASE DETAIL THE HVAC RECEPTACLES REQUIRED ON THE |
| | ROOF. NEC 210.63 |
| | |
| | NEC 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION |
| | EQUIPMENT OUTLET. A 125-VOLT, SINGLE-PHASE, 15- OR |
| | 20-AMPERE-RATED RECEPTACLE OUTLET SHALL BE INSTAL???LED |
| | AT AN ACCESSIBLE LOCATION FOR THE SERVICING OF HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND |
| | WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING, |
| | AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET |
| | SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE |
| | EQUIPMENT DISCONNECTING MEANS. |
| | |
| | 6) DETAIL REQUIRED OUTSIDE RECEPTACLES AT OUTSIDE |
| | PORCHES AND ON THE SECOND FLOOR IF THEY ARE ACCESSIBLE |
| | FROM DWELLING UNITS. NEC 210.52 (E)(2) AND NEC (E)(3) |
| | |
| | NEC 210.52(2) MULTIFAMILY DWELLINGS. FOR EACH DWELLING |
| | UNIT OF A MULTIFAMILY DWELLING WHERE THE DWELLING UNIT |
| | IS LOCATED AT GRADE LEVEL AND PROVIDED WITH INDIVIDUAL |
| | EXTERIOR ENTRANCE/EGRESS, AT LEAST ONE RECEPTACLE |
| | OUTLET READILY ACCESSIBLE FROM GRADE AND NOT MORE THAN |
| | 2.0 M (61???2 FT) ABOVE GRADE LEVEL SHALL BE INSTALLED |
| | |
| | NEC 210. (E)(3) BALCONIES, DECKS, AND PORCHES. |
| | BALCONIES, DECKS, AND PORCHES THAT ARE ATTACHED TO THE |
| | DWELLING UNIT AND ARE ACCESSIBLE FROM INSIDE THE |
| | DWELLING UNIT SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET |
| | ACCESSIBLE FROM THE BALCONY, DECK, OR PORCH. THE |
| | RECEPTACLE OUTLET SHALL NOT BE LOCATED MORE THAN 2.0 M |
| | (61???2 FT) ABOVE THE BALCONY, DECK, OR PORCH WALKING |
| | SURFACE. |
| | |
| | 7) PLEASE RESPOND TO PREVIOUS COMMENT. DETAIL THE |
| | REQUIRED SHOW WINDOW RECEPTACLES IN THE RETAIL SPACES. |
| | NEC 210.62 |
| | |
| | NEC 210.62 SHOW WINDOWS. AT LEAST ONE 125-VOLT, |
| | SINGLE-PHASE, 15- OR 20-AMPERE-RATED RECEPTACLE OUTLET |
| | SHALL BE INSTALLED WITHIN 450 MM (18 IN.) OF THE TOP OF |
| | A SHOW WINDOW FOR EACH 3.7 LINEAR M (12 LINEAR FT) OR |
| | MAJOR FRACTION THEREOF OF SHOW WINDOW AREA MEASURED |
| | HORIZONTALLY AT ITS MAXIMUM WIDTH. |
| | |
| | 8) PLEASE RESPOND TO PREVIOUS COMMENT, PLEASE INDICATE |
| | TYPE FIRE RESISTANCE RATING FOR BUILDING AND THE |
| | APPLICABLE WIRING METHODS TO BE USED. NEC 110.8, NEC |
| | CHAPTER 3 WIRING METHODS AND MATERIALS AND NEC TABLE |
| | ANNEX E |
| | |
| | NEC 110.8 WIRING METHODS. ONLY WIRING METHODS |
| | RECOGNIZED AS SUITABLE ARE INCLUDED IN THIS CODE. THE |
| | RECOGNIZED METHODS OF WIRING SHALL BE PERMITTED TO BE |
| | INSTALLED IN ANY TYPE OF BUILDING OR OCCUPANCY, EXCEPT |
| | AS OTHERWISE PROVIDED IN THIS CODE. |
| | |
| | 9) PLEASE RESPOND TO PREVIOUS COMMENT. VALUE FOR WORK |
| | STATED ON PERMIT APPLICATION APPEARS LOW. PROVIDE A |
| | BREAKDOWN OF ALL MATERIALS AND LABOR, OR, AT YOUR |
| | DISCRETION, PROVIDE A SIGNED CONTRACTOR PROVIDE A |
| | REASONABLE VALUE. WPB F.B.C. 109.3 |
| | |
| | FBC 109.3 THE APPLICANT FOR A PERMIT SHALL PROVIDE AN |
| | ESTIMATED PERMIT VALUE AT TIME OF APPLICATION. PERMIT |
| | VALUATIONS SHALL INCLUDE TOTAL VALUE OF WORK, INCLUDING |
| | MATERIALS AND LABOR, FOR WHICH THE PERMIT IS BEING |
| | ISSUED, SUCH AS ELECTRICAL, GAS, MECHANICAL, PLUMBING |
| | EQUIPMENT AND PERMANENT SYSTEMS. IF, IN THE OPINION OF |
| | THE BUILDING OFFICIAL, THE VALUATION IS UNDERESTIMATED |
| | ON THE APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS |
| | THE APPLICANT CAN SHOW DETAILED ESTIMATES TO MEET THE |
| | APPROVAL OF THE BUILDING OFFICIAL. FINAL BUILDING |
| | PERMIT VALUATION SHALL BE SET BY THE BUILDING OFFICIAL |
| | |
| | 10) PLEASE RESPOND TO PREVIOUS COMMENT. PLEASE INDICATE |
| | THE REQUIRED SIGN LIGHTING OUTLETS FOR EACH COMMERCIAL |
| | SPACE REQUIRED PER NEC 600.5(A) |
| | |
| | NEC 605(A) REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL |
| | BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO |
| | PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE OUTLET |
| | IN AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH |
| | TENANT SPACE FOR SIGN OR OUTLINE LIGHTING SYSTEM USE. |
| | THE OUTLET(S) SHALL BE SUPPLIED BY A BRANCH CIRCUIT |
| | RATED AT LEAST 20 AMPERES THAT SUPPLIES NO OTHER LOAD. |
| | SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED |
| | ACCESSIBLE TO PEDESTRIANS. |
| | |
| | 11) PLEASE RESPOND TO PREVIOUS COMMENT. PLEASE INDICATE |
| | COMPLIANCE WITH THE F.B.C.E.C. C405.2 FOR LIGHTING |
| | CONTROLS IN COMMERCIAL SPACES. FBCEC 405.2 LIGHTING |
| | CONTROLS MANDATORY |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |