Plan Review Notes
Plan Review Notes For Permit 22041189
Permit Number 22041189
Review Stop B
Sequence Number 2
Notes
Date Text
2023-02-28 16:39:16WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22041189
 ADD: 2032 N DIXIE HWY.
 CONT: SOLID ROCK RENOVATION
 TEL: 561-577-3057
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. 2/28/2023
 ACTION: DENIED
 1) 2ND REQUEST. STOP WOK ORDERS WERE GIVEN ON 4/19/22
 FOR ALL TRADES, 8/23/22 STOP WORK ORDER WAS GIVEN FOR
 GAS WORK WITHOUT THE BENEFIT OF A PERMIT. WORK NOT
 INCLUDED IN THE SCOPE OF WORK NEW WINDOWS SHOWN ON
 GOGGLE MAPS. 2 PERMITS WERE REVOKED 12030175 REPLACE 3
 EXT. DOORS, 15070290 REVOKED VALUE $350.00 DOLLARS
 REPLACE BROKEN WINDOWS, 15010327 REISSUE 1212703 FOR
 REPLACE 3 EXTERIOR DOORS. NONE OF THESE PERMITS
 INDICATE NEW WINDOWS FOR THE 2ND STORY PLEASE INCLUDE
 IN THE SCOPE OF WORK. PLEASE PROVIDE THE FOLLOWING
 INFORMATION:
 2) 2ND REQUEST. 2020 FBC-B 1603.1.4 WIND DESIGN
 CRITERIA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 2. RISK CATEGORY.
  
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 3) 2ND REQUESST. COMPONENTS & CLADDING. PLEASE SUBMIT
 THE COMPONENTS AND CLADDING PRODUCT APPROVALS. 2020
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(B) WINDOWS & MULLIONS
  
 4) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 5) SHEET COVERSHEET. SCOPE OF WORK, COMMENTS:
 5A) 2ND REQUEST. NOTE # 2 INDICATES NEW VINYL FLOORING,
 PLEASE DESIGNATE THE LOCATIONS OF FLOORING IN
 RESIDENTIAL UNITS, 2ND STORY CORRIDOR AND STAIRS AND OR
 1ST FLOOR BUSINESS OCCUPANCIES. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6-INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 5A)(1) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 5B)(2) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 5C)(3) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 (TILE & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 OR
 5C)(3) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 ???PILL TEST???
 (CPSC 16 CFR PART 1630) OR WITH ASTM D2859.
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253
  
 5B) SEMI-COMPLIED SHOW AREAS WHERE TO BE REPLACED.
 NOTES 3 & 4 DEAL WITH REPLACEMENT OF DRYWALL BOTH 1/2
 INCH AND 5/8-INCH TYPE X EXACT LOCATIONS ARE NOT GIVEN
 NOR THE AMOUNT OF DRYWALL THAT IS TO BE INSTALLED. 2020
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES.
  
 5B)(1)THE PLANS ARE SILENT AS TO MAINTAINING 1-HOUR
 FIRE RATING SEE 2020 FBC-BUILDING CODE 420.2 SEPARATION
 WALLS AND 420.3 HORIZONTAL SEPARATION. FIRE RATED
 CORRIDORS AND STAIRWAY SECTION 1023.2, SECTION 707 AND
 OR SECTION 711. 1-HOUR FIRE RATING FOR BENEATH THE
 STAIRWAY 1011.7.3. 1ST FLOOR STOCKROOM.
  
 5B)(2) BETWEEN DWELLING UNITS. FBC-B 2020 1207.2
 AIR-BORNE SOUND. WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS FROM EACH OTHER OR
 FROM PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 IF
 FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
  
 5C) 2ND REQUEST. PROVIDE LOCATIONS WHERE WOOD IS
 DAMAGED OR ROTTEN, IT IS UP TO THE DESIGN PROFESSIONAL
 TO GIVE THE CONTRACTORS DIRECTION, IF BEYOND YOUR SCOPE
 THEN AN ENGINEER SHOULD GET INVOLVED. NOTE 5 INDICATES
 REPLACE EXISTING DAMAGED FRAMING OR ROTTEN FRAMING
 ENCOUNTERED PER THE PRESCRIPTIVE METHOD OF THE EXISTING
 BUILDING CODE. PLEASE READ THE SECTIONS 401.2.2 AND
 401.2.2. IN BOTH CASES SUCH MATERIALS SHALL BE
 DETERMINED BY THE BUILDING OFFICIAL TO BE UNSAFE. AGAIN
 PLEASE PROVIDE THE AREAS WHERE DAMAGED OR ROTTEN
 FRAMING MEMBERS ARE LOCATED SIZE OF FRAMING MEMBERS,
 SPACING, SPANS, TYPE OF EXISTING FRAMING AND TYPE OF
 PROPOSED FRAMING, IF TO BE REMOVED, OR IF TO BE
 SISTERED AND THE LENGTH OF THE SISTERED FRAMING MEMBER
 VERSE THE OLD FRAMING MEMBER. PLEASE ALSO REVIEW IN THE
 2020 EXISTING BUILDING CODE 401.3 DANGEROUS CONDITIONS.
 THE BUILDING OFFICIAL SHALL HAVE THE AUTHORITY TO
 REQUIRE THE ELIMINATION OF CONDITIONS DEEMED DANGEROUS.
  
 6) 2ND REQUEST, THE DESIGN PROFESSIONAL GIVES DIRECTION
 TO AMOUNT OF DOORS SO THE CONTRACTOR KNOWS HOW TO BID
 THE PROJECT. NOTE 6 STATES THE GC SHALL REPLACE
 EXISTING INTERIOR DAMAGED INTERIOR DOORS. PLEASE
 PROVIDE LOCATIONS OF THESE DOORS, IF ENTRY DOORS INTO
 THE R2 RESIDENTIAL UNITS THEN THEY SHALL COMPLY WITH
 FBC-BUILDING TABLE 1020.1.
  
 7) 2ND REQUEST PROVIDE LETTER ON EITHER THE DESIGN
 PROFESSIONAL OR CONTRACTOR LETTER HEAD WHERE THESE
 FUNDS ARE TO BE SPENT. FIRST FLOOR. FLORIDA
 ACCESSIBILITY CODE SECTION: DISPROPORTIONATE COST
 202.4.1. PLEASE REVIEW HOW YOU ARE TO MEET
 DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR THE
 DESIGNER OF RECORD ON THEIR LETTERHEAD NEED TO SHOW HOW
 THEY ARE GOING TO SPEND UP TO THE 20% DISPROPORTIONATE
 FUNDS LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE BEING
 SPENT AND IN THE ORDER LISTED IN SECTION 202.4.1
 DISPROPORTIONATE COST OF THE 2020 ACCESSIBILITY CODE.
  
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 ENLARGING DOOR OPENINGS, INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COST
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COST ASSOCIATED WITH RELOCATING
 AN ACCESSIBLE DRINKING FOUNTAIN.
  
 8) 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 8A) 2ND REQUEST. PLEASE STATE WHAT TYPE OF TILE BACKING
 BOARD IS TO BE INSTALLED IN RESTROOMS & BATHROOMS
 THROUGHOUT THE PROJECT.
 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE
 SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS
 THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
  
 10) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  