Plan Review Notes For Permit 22041189
Permit Number 22041189
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-11-21 13:08:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF WORK INVOLVING A 2 STORY
 APARTMENT BUILDING OF 15 LIVING UNITS; HOWEVER, THERE
 IS NO INDICATIONS OF AN EXISTING OR NEW FIRE ALARM
 SYSTEMS.
  
 PER NFPA 101 CH 31 EXISTING APARTMENT BUILDINGS.
  
 31.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 31.3.4.1 GENERAL.
 31.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT OR WITH
 MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE MEETING
 THE REQUIREMENTS
 OF 31.3.4.1.2, SHALL BE PROVIDED WITH A FIRE ALARM
 SYSTEM IN ACCORDANCE
 WITH SECTION 9.6, EXCEPT AS MODIFIED BY 31.3.4.2
 THROUGH 31.3.4.5.
  
 PLEASE REVIEW AND PROVIDE PER THE REQUIREMENT.
  
  
 2) THE 2ND FLOOR MEANS OF EGRESS ARRANGEMENT DOES NOT
 APPEAR TO MEET THE MINIMUM REQUIREMENT
  
 31.2.5 ARRANGEMENT OF MEANS OF EGRESS
  
 31.2.5.3.1 NO COMMON PATH OF TRAVEL SHALL EXCEED 35 FT
 (10.7 M) IN
 BUILDINGS NOT PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH 31.3.5.
 TRAVEL WITHIN A
 DWELLING UNIT SHALL NOT BE INCLUDED WHEN CALCULATING
 COMMON PATH OF
 TRAVEL.
  
  
 3) THE 2ND FLOOR EXIT EXTERIOR STAIR APPEAR TO LAND
 INTO AN FENCE ENCLOSED AREA WITH RESTRICTED EXITING
 CAPACITY AND A GATE.
  
 THERE IS NO INDICATION OF EXIT HARDWARE OR
 LOCKS/LATCHING THAT MEET THE MINIMUM REQUIRMENT FOR AN
 EXIT.
  
 31.2.2.2 DOORS
  
 31.2.2.2.2 DOOR-LOCKING ARRANGEMENTS SHALL COMPLY WITH
 30.2.2.2.2.1,
 30.2.2.2.2.2, 30.2.2.2.2.3, OR 31.2.2.2.2.4.
 31.2.2.2.2.1 NO DOOR IN ANY MEANS OF EGRESS SHALL BE
 LOCKED AGAINST
 EGRESS WHEN THE BUILDING IS OCCUPIED
  
  
  
 4) THERE ARE INDCATIIONS OF A FIRE ESCAPE STAIR WITH
 EXPOSURE TO TO WINDOWS
  
 31.2.2.9 FIRE ESCAPE STAIRS. FIRE ESCAPE STAIRS
 COMPLYING WITH 7.2.8
 SHALL BE PERMITTED
  
 7.2.8.2 PROTECTION OF OPENINGS. FIRE ESCAPE STAIRS
 SHALL BE EXPOSED
 TO THE SMALLEST POSSIBLE NUMBER OF WINDOW AND DOOR
 OPENINGS, AND EACH
 OPENING SHALL BE PROTECTED WITH APPROVED FIRE DOOR OR
 FIRE WINDOW ASSEM BLIES WHERE THE OPENING OR ANY
 PORTION OF THE OPENING IS LOCATED AS
 FOLLOWS:
 (1) HORIZONTALLY, WITHIN 15 FT (4570 MM) OF ANY
 BALCONY, PLATFORM, OR
 STAIRWAY CONSTITUTING A COMPONENT OF THE FIRE ESCAPE
 STAIR
 (2) BELOW, WITHIN THREE STORIES OR 36 FT (11 M) OF ANY
 BALCONY, PLATFORM,
 WALKWAY, OR STAIRWAY CONSTITUTING A COMPONENT OF THE
 FIRE ESCAPE
 STAIR, OR WITHIN TWO STORIES OR 24 FT (7320 MM) OF A
 PLATFORM OR
 WALKWAY LEADING FROM ANY STORY TO THE FIRE ESCAPE STAIR
 (3) ABOVE, WITHIN 10 FT (3050 MM) OF ANY BALCONY,
 PLATFORM, OR WALK WAY, AS MEASURED VERTICALLY, OR
 WITHIN 10 FT (3050 MM) OF ANY STAIR
 TREAD SURFACE, AS MEASURED VERTICALLY
 (4) FACING A COURT SERVED BY A FIRE ESCAPE STAIR, WHERE
 THE LEAST DIMEN SION OF THE COURT DOES NOT EXCEED
 ONE-THIRD OF THE HEIGHT TO THE
 UPPERMOST PLATFORM OF THE FIRE ESCAPE STAIR, MEASURED
 FROM THE
 FINISHED GROUND LEVEL
 (5) FACING AN ALCOVE SERVED BY A FIRE ESCAPE STAIR,
 WHERE THE WIDTH OF
 THE ALCOVE DOES NOT EXCEED ONE-THIRD, OR THE DEPTH OF
 THE ALCOVE
 DOES NOT EXCEED ONE-FOURTH, OF THE HEIGHT TO THE
 UPPERMOST PLATFORM
 OF THE FIRE ESCAPE STAIR, MEASURED FROM THE FINISHED
 GROUND LEVEL
  
 PLEASE REVIEW AND PROVIDE DETAILS FOR THE REQUIREMENT.
  
  
 5) ON THE 1ST FLOOR MIDDLE BUSINESS SPACE THERE APPEARS
 TO BE A STORAGE UNDER THE EXIT STAIR.
  
 31.2.2.3.1 STAIRS. STAIRS COMPLYING WITH 7.2.2 SHALL BE
 PERMITTED.
  
 7.2.2.5.3.2 ENCLOSED, USABLE SPACE SHALL BE PERMITTED
 UNDER STAIRS, PROVIDED THAT BOTH OF THE FOLLOWING
 CRITERIA ARE MET:
 (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR
 ENCLOSURE BY THE SAME
 FIRE RESISTANCE AS THE EXIT ENCLOSURE.
 (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE
 FROM WITHIN THE
 STAIR ENCLOSURE. (SEE ALSO 7.1.3.2.3)
  
 PLEASE REVIEW AND PROVIDE PRETECTION DETAILS.
  
  
 6) ON THE 1ST FLOOR BUSINESSES, 2 OF THE BUSINESS STOCK
 ROOMS DO NOT HAVE EXIT SIGNS THAT WILL LEAD PEOPLE TO
 THAT DOOR TO EXIT INTO THE MAIN ARA.
  
 31.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE
 SIGNS IN ACCORDANCE WITH SECTION 7.10 IN ALL BUILDINGS
 REQUIRING MORE
 THAN ONE EXIT
  
 7.10.1.2 EXITS.
  
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY VISIBLE
 SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE
 EXIT IS NOT READILY
 APPARENT TO THE OCCUPANTS
  
 PLEASE REVIEW AND PROVIDE PRETECTION DETAILS.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL