| 2022-12-19 13:29:17 | ELECTRIC REVIEW FAILED |
| | 1) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR, |
| | OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR |
| | PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3 |
| | 2) PLEASE PROVIDE CLARITY AS TO RISER DIAGRAM |
| | INDICATING A HOUSE PANEL IS NOT METERED AND WITHOUT |
| | MAIN OVERCURRENT PROTECTION. NEC 215.5 |
| | 3) PLEASE PROVIDE CLARITY AS TO SERVICE RISER INDICATES |
| | A 400 AMP MAIN, (19) METERS/DISCONNECTS, HOUSE PANEL |
| | AND UNDERGROUND SERVICE WHEN PREVIOUS ELECTRICAL |
| | SERVICE, PERMITTED PREVIOUSLY ONLY INDICATES A 300 AMP |
| | SERVICE WITH (18) METERS AND DISCONNECTS. IF THIS IS |
| | NEW WORK PLEASE INDICATE ALL EXISTING ELECTRIC AND NEW |
| | PROPOSED ELECTRIC WORK TO BE DONE. FBC 107.2 AND NEC |
| | 215.5 |
| | 4) PANEL SCHEDULES INDICATE SPLIT SYSTEM AIR |
| | CONDITIONING. PLEASE DETAIL THE OUTDOOR CONDENSER UNITS |
| | ON ELECTRIC FLOOR PLAN. FBC 107.2 |
| | 5) PLEASE INDICATE TYPE FIRE RESISTANCE RATING FOR |
| | BUILDING AND THE APPLICABLE WIRING METHODS TO BE USED. |
| | FBC 107.2 |
| | 6) PLEASE INDICATE VIA NOTE ON PLAN THAT FIRE ALARM AND |
| | OTHER LOW VOLTAGE SYSTEMS REQUIRE A SEPARATE PERMIT. |
| | 7) PLEASE INDICATE APPLICABLE CIRCUITS TO COMPLY WITH |
| | NEC 210.12 ARC FAULT PROTECTION ON PANEL SCHEDULES AND |
| | FLOOR PLANS. |
| | 8) PLEASE INDICATE COMPLIANCE WITH NEC 210.62 FOR SHOW |
| | WINDOW RECEPTACLES IN COMMERCIAL SPACES. |
| | 9) PLEASE INDICATE THE REQUIRED SIGN LIGHTING OUTLETS |
| | REQUIRED PER NEC 600.5 FOR EACH COMMERCIAL SPACE |
| | 10) PLEASE INDICATE COMPLIANCE WITH THE F.B.C.E.C. |
| | C405.2 FOR LIGHTING CONTROLS IN COMMERCIAL SPACES |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |