Notes
Date Text
2022-09-06 13:16:48JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL1654-R29 SYSTEM NO. W-212 MAXIMUM DESIGN
 PRESSURE -105 IS A FULLY BONDED SYSTEM AND DO NOT MEET
 THE MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF
 -108.17 FOR EXPOSURE CATEGORY C AREAS. FOR ASSEMBLIES
 WITH ALL COMPONENTS FULLY BONDED IN PLACE, THE MAXIMUM
 DESIGN PRESSURE FOR THE SELECTED ASSEMBLY SHALL MEET OR
 EXCEED CRITICAL DESIGN PRESSURE DETERMINED IN
 ACCORDANCE WITH FBC R CHAPTER 3. NO RATIONAL ANALYSIS
 IS PERMITTED FOR THESE SYSTEMS AS PER LIMITATIONS
 #5.7.3. PROVIDE SYSTEM THAT COMPLIES.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  