2022-05-05 10:30:02REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) BUILDING WAS BUILT UNDER THE FBC FHA REQUIREMENTS
 AND IS REQUIRED TO MAINTAIN THOSE REQUIREMENTS -
 KITCHEN LAYOUT DOES NOT APPEAR TO COMPLY WITH FBC FHA
 REQUIREMENT 7 - USABLE KITCHENS AND BATHROOMS.
 SECTION 100.205(C)(3)(IV) REQUIRES THAT COVERED
 MULTIFAMILY DWELLINGS WITH A BUILDING ENTRANCE ON AN
 ACCESSIBLE ROUTE SHALL BE DESIGNED AND CONSTRUCTED IN
 SUCH A MANNER THAT ALL PREMISES WITHIN COVERED
 MULTIFAMILY DWELLING UNITS CONTAIN USABLE KITCHENS AND
 BATHROOMS SUCH THAT AN INDIVIDUAL IN A WHEELCHAIR CAN
 MANEUVER ABOUT THE SPACE. (1)USABLE KITCHENS. USABLE
 KITCHENS WOULD MEET SECTION 100.205(C)(3)(IV) IF:
  
 (A)A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 THAT ALLOWS A PARALLEL APPROACH BY A PERSON IN A
 WHEELCHAIR IS PROVIDED AT THE RANGE OR COOKTOP AND SINK
 AND EITHER A PARALLEL OR FORWARD APPROACH IS PROVIDED
 AT OVEN, DISH WASHER, REFRIGERATOR/FREEZER OR TRASH
 COMPACTOR. (SEE FIGURE FHAG-6)
  
 CITY OF WEST PALM BEACH HAS AN EXCEPTION FORM - PLEASE
 E MAIL ME IF YOU WOULD LIKE A COPY - [email protected]