Plan Review Notes
Plan Review Notes For Permit 22041103
Permit Number 22041103
Review Stop P
Sequence Number 1
Notes
Date Text
2022-04-28 08:27:251ST 2ND 3RD PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 604.2 SYSTEM INTERCONNECTION. AT THE POINTS
 OF INTERCONNECTION BETWEEN THE HOT AND COLD WATER
 SUPPLY PIPING SYSTEMS AND THE INDIVIDUAL FIXTURES,
 APPLIANCES OR DEVICES, PROVISIONS SHALL BE MADE TO
 PREVENT FLOW BETWEEN SUCH PIPING SYSTEMS. YOUR
 ISOMETRIC SHOW THE HOT AND COLD INTERCONNECTED AT
 P-14/P-19.
  
 2. 2020 FEC C404.6.1 - THE RETURN LINE OF THE LOOP IS
 TO BE A DEDICATED RETURN LINE.
  
 3. 2020 FEC C404.5.1 - THE MAXIMUM ALLOWABLE PIPE
 LENGTH FROM THE NEAREST HEAT SOURCE OF HEATED WATER TO
 THE FIXTURE SUPPLY SHALL BE ACCORDING TO TABLE
 C404.5.1.
  
 4. 61G1-16 AND 61G15, F.A.C ALL ELECTRONIC DOCUMENTS
 PREPARED BY ARCHITECTS OR ENGINEERS MUST BE DIGITALLY
 SIGNED,
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  