Plan Review Notes
Plan Review Notes For Permit 22041024
Permit Number 22041024
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-05-04 10:39:42FIRE COMMENTS:
 (1) AFTER INSTALLATION COMPLETED, THE CONTRACTOR SHALL
 PROVIDE A SIGNED AND DATED RECORD OF COMPLETION.
 (2) A 24- HOUR BATTERY TEST WILL BE REQUIRED FOR THE
 FACP AND VERIFIED BY AN INSPECTOR FROM THE WEST PALM
 BEACH FIRE PREVENTION BUREAU.
 (3) WIRELESS MONITORING WILL BE VERIFIED BY AN
 INSPECTOR FROM THE WEST PALM BEACH FIRE PREVENTION
 BUREAU UNDER NORMAL POWER AND UNDER BATTERY POWER.
  