Plan Review Notes
Plan Review Notes For Permit 22040988
Permit Number 22040988
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-04-22 11:50:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN ADDRESS INDICATION ON THE APPLICATION OF
 205 N DIXIE HWY, HOWEVER, THE SINGLE PLAN SHEET
 SUBMITTAL INDICATES 300 PALM BEACH LAKES BLVD.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE CORRECT
 LOCATION AND CORRECT THE APPLICABLE DOCUMENT.
  
  
 2) THERE ARE NO DOCUMENT/MANUFACTURES SPEC SHEETS
 INDICATING THE PROPOSED GATES.
  
 PLEASE PROVIDE.
  
  
 2A) THERE ARE NO DOCUMENT/MANUFACTURES SPEC SHEETS
 INDICATING THE CARD READERS AND APPLICABLE ASSOCIATED
 EQUIPMENT..
  
 PLEASE PROVIDE.
  
  
 3) THERE IS AN INDICATION OF FIRE SPRINKLER HEAD
 RELOCATION DUE TO THE GATE INSTALLATIONS, HOWEVER,
 THERE IS NO INDICATION THAT THE FIRE SPRINKLER WORK
 SHALL BE SUBMITTED UNDER SEPARATE PERMIT AND DSHOP
 DRAWINGS.
  
 PLEASE PROVIDE THE APPLICABLE NOTE THAT THE FIRE
 SPRINKLER WORK SHALL BE SUBMITTED UNDER SEPARATE PERMIT
 AND DSHOP DRAWINGS.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  