| Plan Review Notes For Permit 22040988 |
| Permit Number |
22040988 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-22 11:50:19 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN ADDRESS INDICATION ON THE APPLICATION OF | | | 205 N DIXIE HWY, HOWEVER, THE SINGLE PLAN SHEET | | | SUBMITTAL INDICATES 300 PALM BEACH LAKES BLVD. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE CORRECT | | | LOCATION AND CORRECT THE APPLICABLE DOCUMENT. | | | | | | | | | 2) THERE ARE NO DOCUMENT/MANUFACTURES SPEC SHEETS | | | INDICATING THE PROPOSED GATES. | | | | | | PLEASE PROVIDE. | | | | | | | | | 2A) THERE ARE NO DOCUMENT/MANUFACTURES SPEC SHEETS | | | INDICATING THE CARD READERS AND APPLICABLE ASSOCIATED | | | EQUIPMENT.. | | | | | | PLEASE PROVIDE. | | | | | | | | | 3) THERE IS AN INDICATION OF FIRE SPRINKLER HEAD | | | RELOCATION DUE TO THE GATE INSTALLATIONS, HOWEVER, | | | THERE IS NO INDICATION THAT THE FIRE SPRINKLER WORK | | | SHALL BE SUBMITTED UNDER SEPARATE PERMIT AND DSHOP | | | DRAWINGS. | | | | | | PLEASE PROVIDE THE APPLICABLE NOTE THAT THE FIRE | | | SPRINKLER WORK SHALL BE SUBMITTED UNDER SEPARATE PERMIT | | | AND DSHOP DRAWINGS. | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|