| 2022-06-01 14:07:43 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22040982 |
| | 6/1/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A4.22 DETAIL 1: SHOW THE CLEAR FLOOR SPACE |
| | DIMENSIONS FOR THE WATER CLOSET AND LAVATORY- SECS. |
| | 604.3 & 606.2 FBC ACC. PLEASE NOTE THAT THE DOOR SHALL |
| | NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR THE |
| | LAVATORY- SEC. 603.2.3 FBC ACC. |
| | |
| | 2) P0.1: THE BOARDROOM SINK FIXTURE DRAIN SHALL NOT |
| | CONNECT INTO THE BATHROOM WET VENT, AND SHALL DISCHARGE |
| | DOWNSTREAM OF THE VENT- SEC. 912.1 FBC P. |
| | |
| | 3) P2.1: INSTALLATION OF NEW DRAIN OUTLETS MAY REQUIRE |
| | THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE |
| | REINFORCING STEEL OR POST STRESSED FLOOR TENDONS. |
| | PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE |
| | WILL BE MET- SECTION 107.2.1 WPB. |
| | |
| | 4) P2.1: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING |
| | SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR |
| | SPACE AROUND THE PIPING. PROVIDE A UL TESTED AND |
| | APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- |
| | SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |